83-507-013 Rev. D

16

4.

Route the AC wires to the input connector terminals as required. To connect the wires, loosen the
terminal screw, insert the stripped wire into the terminal and tighten the screw securely (4.4-5.3 Lb-inch).

5.

Route the wires inside the cover to prevent pinching. Fasten the cover to the unit using the M3x8 Flat
Head screws provided. Refer to Fig.3-3 for details.

3.8 TURN-ON CHECKOUT PROCEDURE

3.8.1

General

The following procedure ensures that the power supply is operational and may be used as a basic in-
coming inspection check. Refer to Fig. 4-1 and fig. 4-2 for the location of the controls indicated in the
procedure.

3.8.2

Prior to Operation

1. Ensure that the power supply is configured to the default setting:

On/Off switch at Off position.

 Dip switch: All positions at Down (“Off”) position.

 J2 Sense connector: Configured to Local Sense as shown in Fig. 3-4:

 For units equipped with IEEE option, ensure that the IEEE_En switch is in Up (default) po-

sition (Refer to Fig.4-2, Item 9 for location) if checkout is to be done in IEEE mode.

Fig.3-3: AC input cover and strain relief, 1500W models

Cover

Assembled Strain Relief

M3x8

Flat Head screws

(2 places)

L N

1 Remote (+) sense
2 Local (+) sense
3 Not connected
4 Local (-) sense
5 Remote (-) sense

Fig.3-4: J2 Sense connector default connection

Plug P/N: MC1,5/5-ST-3,81
(Phoenix)