83-507-013 Rev. D

30

Table 4-2: Rear panel connections and controls

Number

Item

Description

Section

1

AC input
connector

Wire clamp connector for 1500W units.
IEC connector for 750W units.

3.7.1
3.7.2

2

DC output

Bus-bars for 6V to 60V models.
Wire clamp connector for 80V to 600V models.

3.9.6

3

Remote-In
connector

RJ-45 type connector, used for connecting power supplies to
RS232 or RS485 port of computer for remote control purposes.
When using several power supplies in a power system, the first
unit Remote-In is connected to the computer and the remaining
units are daisy-chained, Remote-In to Remote-Out.

7.3

7.5

4

Remote Out
connector

RJ-45 type connector, used for daisy-chaining power supplies to
form a serial communication bus.

7.3
7.5

5

J1 Analog
Remote
connector

Connector for remote analog interface. Includes Output Voltage
and Current programming and monitoring signals, Shut-off control
(electrical signal), Enable/Disable control (dry-contact), Power
Supply OK (PS_OK) signal and operation mode (CV/CC) signal.

6

SW1 Setup
switch

Nine position DIP-switch for selecting remote programming and
monitoring modes for Output Voltage, Output Current and other
control functions.

4.4

7

J2 Remote
sense
connector

Connector for making remote sensing connections to the load for
regulation of the load voltage and compensation of load wire drop.

3.10

3.8.2

8

Blank
Sub-plate

Blank sub-plate for standard units. Isolated Remote Analog pro-
gramming connector for units equipped with Isolated Analog con-
trol option. IEEE connector for units equipped with IEEE pro-
gramming option (shown).

Fig.4.2

9

IEEE switch

Two position DIP-switch for selecting IEEE mode or RS232/RS485
mode when IEEE option is installed.

Fig.4.2

10

Ground
screw

M4x0.7,

8mm

long

DBL-SEMS

screw

for

chassis

ground

connection.

Fig.4.2

4.4 REAR PANEL SW1 SETUP SWITCH

The SW1 Setup switch (see Fig.4-3) is a 9-position DIP-switch that allows the user to choose the
following:

 Internal or remote programming for Output Voltage and Output Current.

 Remote voltage or resistive programming of Output Voltage and Output Current limit.

 Select range of remote voltage and resistive programming.

 Select range of output Voltage and Output Current monitoring.

 Select the Remote Shut-Off control logic.

 Select between RS232 and RS485 communication interface.

 Enable or disable the rear panel Enable/Disable control (dry contact).