Chapter 6 remote analog programming – TDK GENESYS 1500W User Manual

Page 53

Advertising
background image

83-507-013 Rev. D

45

CAUTION

COM (J1-12), VPGM_RTN (J1-22) AND IPGM_RTN (J1-23) terminals of J1
connect internally to the –Sense potential (-S). Do not connect these termi-
nals to any potential other than –Sense (-S), as it may damage the power
supply.

CHAPTER 6 REMOTE ANALOG PROGRAMMING

6.1 INTRODUCTION

The rear panel connector J1 allows the user to program the power supply Output Voltage and Current
with an analog device. J1 also provides monitoring signals for Output Voltage and Output Current.
The programming range and monitoring signals range can be selected between 0-5V or 0-10V using
the setup switch SW1. When the power supply is in Remote Analog programming mode, the serial
communication port is active and can be used to query the power supply settings.

6.2 LOCAL/REMOTE ANALOG INDICATION

Contact 8 of J1 (Fig.4-2, Item 5) accepts TTL signal or Open-Short contact (referenced to J1-12) to
select between Local or Remote Analog programming of the Output Voltage and Current.
In Local mode, the Output Voltage and Output Current can be programmed via the front panel
VOLTAGE and CURRENT encoders or via the RS232/RS485 port. In Remote Analog mode, the Out-
put Voltage and current can be programmed by analog voltage or by programming resistors via J1
contacts 9 and 10 (refer to Sections 6.4 and 6.5). Refer to Table 6-1 for Local/Remote Analog control
(J1-8) function and Setup switch SW1-1, 2 settings.

SW1-1, 2 setting

J1-8 function

Output Voltage/
Current setting

Down (default)

No effect

Local

“0” or Short

Remote

Up

“1” or Open

Local

Table 6-1: Local/Remote Analog control function

6.3 LOCAL/REMOTE ANALOG INDICATION

Contact 21 of J1 (Fig. 4-2, Item 5) is an open collector output that indicates if the power supply is in
Local mode or in Remote Analog mode. To use this output, connect a pull-up resistor to a voltage
source of 30Vdc maximum. Choose the pull-up resistor so that the sink current will be less than 5mA
when the output is in a low state. Refer to table 6-2 for J1-21 function.

J1-8

SW1-1

SW1-2

J1-21 signal

Mode

Down

Down

Open

Local (FP)

Down

Up

00.6V

Remote Analog

Up

Down

00.6V

Remote Analog

TTL “0” or short

Up

Up

00.6V

Remote Analog

TTL “1” or open

Down or Up

Down or Up

Open

Local (FP)

Table 6-2: Local/Remote Analog indication

Advertising