Temperatures and flows, Temperature and flows, English units) – York UL R134A User Manual

Page 10

Advertising
background image

JOHNSON CONTROLS

10

Temperatures and Flows

TEMPERATURE AND FLOWS

(English Units)

NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls office for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest Johnson Controls office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.

MODEL

NUMBER

YCIV

LEAVING WATER

TEMPERATURE (°F)

COOLER

3

FLOW

(GPM)

AIR ON CONDENSER (°F)

MIN.

1

MAX.

2

MIN.

MAX.

MIN.

MAX

50 Hz

60 Hz

0600(S/P)

0157(S/P)

40

60

140

675

0

125

0590(E/V)

0157(E/V)

40

60

160

750

0

125

0650(S/P)

0177(S/P)

40

60

160

750

0

125

0630(E/V)

0177(E/V)

40

60

160

750

0

125

0720(S/P/)

0187(S/P)

40

60

160

750

0

125

0700(E/V)

0187(E/V)

40

60

160

750

0

125

0760(E/V)

0197(E/V)

40

60

180

750

0

125

0770(S/P)

0207(S/P)

40

60

180

800

0

125

0800(E/V)

0207(E/V)

40

60

180

750

0

125

0840(S/P)

0227(S/P)

40

60

180

800

0

125

0830(E/V)

0227(E/V)

40

60

180

750

0

125

0920(S/P)

0247(S/P)

40

60

180

800

0

125

0930(E/V)

0247(E/V)

40

60

180

800

0

125

1000(S/P)

0267(S/P)

40

60

180

800

0

125

1050(E/V)

0267(E/V)

40

60

250

1200

0

125

1070(S/P)

0287(S/P)

40

60

250

1200

0

125

1120(E/V)

0287(E/V)

40

60

250

1200

0

125

1180(S/P)

0307(S/P)

40

60

300

1200

0

125

1220(E/V)

0327(E/V)

40

60

300

1200

0

125

1340(S/P)

0357(S/P)

40

60

300

1200

0

125

1380(E/V)

0357(E/V)

40

60

300

1200

0

125

1500(S/P)

0397(S/P)

40

60

300

1200

0

125