Refrigerant r-134a – York UL R134A User Manual

Page 61

Advertising
background image

JOHNSON CONTROLS

FORM 201.23-EG1 (1007)

61

Refrigerant R-134a

STANDARD EFFICIENCY

MODEL NUMBER (YCIV____ S/P)

General Unit Data

60Hz

0287

0307

0357

0397

50Hz

1070

1180

1340

1500

Number of Independent Refrigerant Circuits

3

3

3

3

Refrigerant Charge, R-134a, Ckt.-1/Ckt.-2, kg.

84 / 77 / 77

84 / 84 / 77

84 / 84 / 105

105 / 105 / 105

Oil Charge, Ckt.-1/Ckt.-2, liters

19 / 15 / 15

19 / 19 / 15

19 / 19 / 19

19 / 19 / 19

Glycol Charge (43% concentration), liters

0

0

0

0

Compressors, Semihermetic Screw
Quantity per Chiller

3

3

3

3

Condensers, High Efficiency Fin/Tube with Integral Subcooler
Total Chiller Coil Face Area, m

2

35

38

44

49

Number of Rows

3

3

3

3

Fins per meter

669

669

669

669

Condenser Fans
Number, Ckt.-1/Ckt.-2

5/4/4

5/5/4

5/5/6

6/6/6

Low Noise Fans
Fan Motor, HP/kWi

2/1.50

2/1.50

2/1.50

2/1.50

Total Chiller Airflow, l/sec.

79768

85904

98176

110448

Ultra Quiet Fans
Fan Motor, HP/kWi

2/1.50

2/1.50

2/1.50

2/1.50

Total Chiller Airflow, l/sec.

79768

85904

98176

110448

Dual Speed Fans - Normal Speed
Fan, KWi

1.5

1.5

1.5

1.5

Total Chiller, m3/s

67

67

78

78

Dual Speed Fans - Lower Speed
Fan, KWi

1.5

1.5

1.5

1.5

Total Chiller, m3/s

52

52

59

59

High Static Fans
Fan, KWi

3.7

3.7

3.7

3.7

Total Chiller, m3/s

80

86

98

110

Evaporator, Direct Expansion
Water Volume, liters

764.6

893.3

893.3

893.3

Maximum Water Side Pressure, Bar

10

10

10

10

Maximum Refrigerant Side Pressure, Bar

16

16

16

16

Minimum Chilled Water Flow Rate, l/sec.

16

19

19

19

Maximum Chilled Water Flow Rate, l/sec.

76

76

76

76

Water Connections, mm

245

245

245

245

Contact your nearest Johnson Controls Sales Office for weight data.