Standard efficiency ratings – York UL R134A User Manual

Page 26

Advertising
background image

JOHNSON CONTROLS

26

MODEL:YCIV0267S/P

AIR TEMPERATURE ON - CONDENSER (°C)

LCWT

25.0

30.0

35.0

40.0

45.0

46.0

(°C)

KWo

KWi

COP

KWo

KWi

COP

KWo

KWi

COP

KWo

KWi

COP

KWo

KWi

COP

KWo

KWi

COP

5.0

898.1

224.4

3.7

883.4

254.8

3.2

866.4

288.2

2.8

838.4

322.8

2.4

796.3

349.6

2.2

787.8

354.9

2.1

6.0

923.0

226.2

3.8

907.7

256.6

3.3

889.9

290.2

2.9

859.6

323.9

2.5

816.0

350.8

2.2

807.2

356.2

2.1

7.0

948.4

228.2

3.8

932.5

258.5

3.4

913.9

292.1

2.9

881.1

325.0

2.6

836.1

352.0

2.3

823.0

354.5

2.2

8.0

974.1

230.3

3.9

957.7

260.5

3.4

938.4

294.1

3.0

902.9

326.1

2.6

856.7

353.2

2.3

830.7

346.5

2.3

9.0

1000.4 232.5

4.0

983.4

262.6

3.5

963.2

296.3

3.0

924.9

327.3

2.7

877.6

354.4

2.3

838.5

338.4

2.3

10.0

1027.2 234.8

4.0

1009.5 264.8

3.5

988.6

298.4

3.1

947.5

328.5

2.7

894.1

352.2

2.4

846.3

330.4

2.4

11.0

1054.4 237.3

4.1

1036.0 267.2

3.6

1014.5 300.6

3.2

970.4

329.6

2.8

902.4

343.6

2.5

854.0

322.4

2.5

12.0

1081.9 240.0

4.2

1063.1 269.6

3.7

1040.8 302.9

3.2

993.6

330.9

2.8

910.6

335.1

2.6

861.4

314.7

2.6

13.0

1110.1 241.5

4.2

1090.4 272.1

3.7

1067.6 305.4

3.3

1017.3 332.1

2.9

918.5

326.8

2.7

868.2

307.6

2.7

MODEL:YCIV0287S/P

AIR TEMPERATURE ON - CONDENSER (°C)

LCWT

25.0

30.0

35.0

40.0

45.0

46.0

(°C)

KWo

KWi

COP

KWo

KWi

COP

KWo

KWi

COP

KWo

KWi

COP

KWo

KWi

COP

KWo

KWi

COP

5.0

954.4

236.0

3.7

936.9

271.1

3.2

916.5

309.6

2.8

877.6

343.2

2.4

793.2

350.5

2.1

746.0

331.2

2.1

6.0

981.3

237.5

3.8

963.2

272.4

3.3

942.0

311.0

2.8

899.5

343.6

2.5

800.8

343.6

2.2

754.0

324.7

2.2

7.0

1008.7 239.2

3.9

990.1

273.8

3.4

967.5

312.0

2.9

921.4

343.8

2.5

809.9

337.1

2.3

763.4

318.9

2.2

8.0

1036.6 241.0

3.9

1017.4 275.2

3.4

992.9

312.7

3.0

943.6

344.0

2.6

820.0

330.9

2.3

772.1

312.5

2.3

9.0

1065.0 243.1

4.0

1045.3 276.9

3.5

1018.8 313.5

3.0

966.3

344.1

2.6

829.3

324.3

2.4

780.4

306.1

2.4

10.0

1093.8 245.4

4.1

1073.7 278.7

3.6

1045.2 314.4

3.1

989.4

344.2

2.7

838.5

317.7

2.5

787.8

299.7

2.5

11.0

1123.1 248.0

4.2

1102.5 280.7

3.6

1071.9 315.4

3.2

1012.6 344.3

2.8

847.0

311.1

2.5

794.9

293.5

2.5

12.0

1152.9 250.7

4.2

1131.8 282.9

3.7

1099.0 316.5

3.3

1036.2 344.4

2.8

855.1

304.7

2.6

801.6

287.2

2.6

13.0

1183.2 253.6

4.3

1161.7 285.3

3.8

1126.6 317.6

3.3

1060.1 344.5

2.9

862.0

298.3

2.7

808.3

281.1

2.7

MODEL:YCIV0307S/P

AIR TEMPERATURE ON - CONDENSER (°C)

LCWT

25.0

30.0

35.0

40.0

45.0

46.0

(°C)

KWo

KWi

COP

KWo

KWi

COP

KWo

KWi

COP

KWo

KWi

COP

KWo

KWi

COP

KWo

KWi

COP

5.0

1060.5 260.2

3.7

1041.2 300.1

3.2

1019.7 344.5

2.8

975.0

381.9

2.4

870.2

379.2

2.2

817.1

356.4

2.2

6.0

1090.3 262.0

3.8

1070.2 301.3

3.3

1046.9 345.3

2.8

998.2

381.7

2.5

878.4

371.1

2.2

826.0

349.2

2.2

7.0

1120.9 263.9

3.9

1099.9 302.6

3.4

1074.3 345.7

2.9

1022.0 381.3

2.5

888.4

363.6

2.3

835.5

342.1

2.3

8.0

1152.1 266.2

4.0

1130.1 304.1

3.5

1102.2 346.2

3.0

1046.2 380.8

2.6

897.9

355.6

2.4

844.5

334.7

2.4

9.0

1183.8 268.8

4.1

1161.0 305.9

3.5

1130.7 346.9

3.1

1070.9 380.2

2.7

907.5

347.9

2.4

853.1

327.6

2.4

10.0

1216.2 271.7

4.1

1192.5 307.9

3.6

1159.8 347.7

3.1

1095.9 379.6

2.7

916.7

340.3

2.5

860.8

320.7

2.5

11.0

1249.2 274.8

4.2

1224.5 310.3

3.7

1189.3 348.6

3.2

1121.1 379.1

2.8

925.4

333.0

2.6

868.4

313.9

2.6

12.0

1282.9 278.4

4.3

1257.3 312.9

3.7

1219.4 349.7

3.3

1147.0 378.5

2.9

933.7

326.0

2.7

875.7

307.2

2.7

13.0

1317.1 282.4

4.3

1290.6 315.7

3.8

1249.9 351.1

3.3

1173.3 378.0

2.9

941.3

319.2

2.8

883.0

300.7

2.7

Standard Efficiency Ratings

– SI - 460V/60Hz

NOTES:

1. kWo

= Unit kW Cooling Capacity Output

2. kWi

= Compressor kW Input

3. COP

= Coefficient of Performance (includes condenser fan power)

4. LCWT = Leaving Chilled Water Temperature

5. Ratings based on 0.15 l/s cooler water per ton, and 0.018 (m

2

– °C)/kW

Advertising