Specifications, Continued – York UL R134A User Manual

Page 6

Advertising
background image

JOHNSON CONTROLS

6

and schedule, (variable) out of range, remote input

indication, chilled liquid reset setpoint, and history

data for last ten shutdown faults. Compressor suc-

tion, discharge, and oil pressures and temperatures,

suction and discharge superheats, percent of full-load,

operating hours, starts, and anti-recycle timer status.

Status Messages for manual override, unit switch off,

compressor run, run permissive, remote controlled

shut down, no cooling load, daily/holiday shut down,

anti-recycle timer.

• During extreme or unusual conditions (i.e. blocked

condenser coils, ambient above scheduled maximum,

etc.) the chiller control system will avoid safety shut-

down by varying the chiller controls and cooling load

output to stay online and avoid safety limits being

reached. This allows maximum possible cooling ca-

pacity until the unusual condition is cleared and avoids

costly shutdowns. The system monitors the following

parameters and maintain the maximum cooling output

possible without shutdown of the equipment: motor

current, suction pressure and discharge pressure.

• System Safeties are provided for individual compres-

sor systems to perform auto-reset shut down (manual

reset required after the third trip in 90 minutes). Safe-

ties include: high discharge pressure or temperature,

low suction pressure, high / low motor current, high

motor temperature, high pressure switch, high / low

differential oil pressure, high oil temperature, low suc-

tion superheat, critical sensor malfunction, low or high

current, phase loss/single phase power, overload of

motor windings, and low voltage.

• Unit Safeties are provided for the chiller to perform

auto-reset shut down for the following conditions: high

or low ambient, low leaving chilled liquid temperature,

under voltage, and flow switch operation.

COMPLETE FACTORY PACKAGE

• These air cooled chillers are shipped as a complete

factory package. Each unit is completely assembled

with all interconnecting refrigerant piping and internal

wiring, ready for field installation:

• Each compressor is installed on its own independent

refrigerant circuit, which is factory pressure tested,

evacuated, then fully charged with R134a refrigerant

and oil.

• After assembly, an operational test is performed with

water flowing through the cooler to ensure each circuit

operates correctly.

• Unit panels, structural elements, control boxes and

heavy gauge structural base shall be constructed

of galvanized steel. Unit panels, control boxes and

structural base are finished with a baked on powder

paint. All painted surfaces shall be coated with baked

on powder paint which, when subject to ASTMB117,

1,000 hour, 5% salt spray test, yields minimum ASTM

1654 rating of “6”.

• Design is IAW applicable sections of ASME Pressure

Vessel Code, NFPA 70 (National Electrical Code), U.L.

and cU.L. Standards , and ASHRAE/ANSI-15 Safety

Code for Mechanical Refrigeration.

• Units are Rated (all) and Certified (140 - 200 tons) IAW

ARI Standard 550/590-98.

• Design is IAW ASHRAE 90.1 Energy Standard for

Building Except Low-Rise Residential Buildings and

ARI 70 Sound Rating of Large Outdoor Refrigeration

and Air Conditioning Equipment.

• YCIV chillers are designed within EN ISO 9001 and

built within an EN ISO 9002 accredited manufacturing

organization.

• All exposed power wiring routed through liquid-tight,

UV-stabilized, non-metallic conduit.

• When required, chillers have the option available to

conform with the following European Directives (50

Hz only):

♦ Machinery Directive (89/9/EEC)
♦ Low Voltage Directive (7//EEC, EN 600)
♦ EMC Directive (89/6/EEC)
♦ Pressure Equipment Directive (97//EC)
♦ Safety Code for Mechanical Refrigeration (EN78)

Specifications

(Continued

)