Refrigerant r-134a – York UL R134A User Manual

Page 57

Advertising
background image

JOHNSON CONTROLS

FORM 201.23-EG1 (1007)

57

Contact your nearest Johnson Controls Sales Office for weight data.

Refrigerant R-134a

STANDARD EFFICIENCY

MODEL NUMBER (YCIV____ S/P)

General Unit Data

60Hz

0287

0307

0357

0397

50Hz

1070

1180

1340

1500

Number of Independent Refrigerant Circuits

3

3

3

3

Refrigerant Charge, R-134a, Ckt.-1/Ckt.-2, lbs

185/170/170

185/185/170

185/185/230

230/230/230

Oil Charge, Ckt.-1/Ckt.-2, gal.

5/4/4

5/4/4

5/5/5

5/5/5

Glycol Charge (43% concentration), gal

5.4

5.5

6.0

6.3

Comp.s, Semihermetic Screw
Quantity per Chiller

3

3

3

3

Condensers, High Efficiency Fin/Tube with Integral Subcooler
Total Chiller Coil Face Area, ft2

381

411

469

528

Number of Rows

3

3

3

3

Fins per Inch

17

17

17

17

Condenser Fans
Number, Ckt.-1/Ckt.-2

5/4/4

5/4/4

5/5/6

6/6/6

Low Noise Fans
Fan Motor, HP/kWi

2/1.8

2/1.8

2/1.8

2/1.8

Total Chiller Airflow, cfm

169000

182000

208000

234000

Ultra Quiet Fans
Fan Motor, HP/kWi

2/1.50

2/1.50

2/1.50

2/1.50

Total Chiller Airflow, cfm

169000

182000

208000

234000

Dual Speed Fans - Normal Speed
Fan Motor, hp

2

2

2

2

Total Chiller, CFM

143000

143000

165000

165000

Dual Speed Fans - Lower Speed
Fan Motor, hp

2

2

2

2

Total Chiller, CFM

109200

109200

126000

126000

High Static Fans
Fan Motor, hp

5

5

5

5

Total Chiller, CFM

169000

182000

208000

234000

Evaporator, Direct Expansion
Water Volume, gals.

202.0

236.0

236.0

236.0

Maximum Water Side Pressure, PSIG

150

150

150

150

Maximum Refrigerant Side Pressure, PSIG

235

235

235

235

Minimum Chilled Water Flow Rate, gpm

250

300

300

300

Maximum Chilled Water Flow Rate, gpm

1200

1200

1200

1200

Water Connections, inches

10

10

10

10

Advertising