York UL R134A User Manual

Page 5

Advertising
background image

JOHNSON CONTROLS

FORM 201.23-EG1 (1007)

5

• Discharge line provided with manual compressor

shutoff service valve (See Options and Accessories for

suction line valve). Suction line equipped with closed-

cell insulation.

• Insulated external oil separators with no moving parts,

450 PSIG (31 bar) design working pressure, and UL

listing. Refrigerant system differential pressure pro-

vides oil flow through service replaceable, 0.5 micron,

full flow, cartridge type oil filter internal to compres-

sor.

• Oil cooling provided by dedicated air cooled finned

tube type heat exchanger located in the condenser

section of the machine.

• A flash tank is located in each refrigerant circuit to

increase the system efficiency. The design working

pressure is 450 PSIG (31 bar).

• Suction lines, oil separators and flash tanks are cov-

ered with closed-cell insulation.

EVAPORATOR

• High efficiency, direct-expansion type cooler with re-

frigerant in tubes and chilled liquid through the baffled

shell. Independent circuits provided for each compres-

sor.

• Design working pressure of the shell waterside is 150

PSIG (10.3 bar), and 235 PSIG (16 bar) for the refrig-

erant side. Constructed and tested IAW applicable

sections of ASME Pressure Vessel Code, Section VIII,

Division (1). Water side exempt per paragraph U-1, ©,

(6).

• Removable heads allow access to internally-en-

hanced, seamless, copper tubes. Water vent and drain

connections included.

• The evaporator is equipped with a thermostatically

controlled heater for protection to -20°F (-29°C) am-

bient, and shell is covered with 3/4” (19mm), flexible,

closed-cell insulation, thermal conductivity of 0.26k

(BTU/HR-Ft

2

-°F/in.) maximum.

• Water nozzles have grooves for mechanical (ANSI/

AWWA C-606) couplings, and shall be insulated by

Contractor after pipe installation. (See the Accessories

and Options section for flange options.

CONDENSER SECTION

• Condenser fans are dynamically and statically bal-

anced, direct drive, corrosion resistant glass fiber

reinforced composite blades molded into low noise,

full airfoil cross section, providing vertical air discharge

from extended orifices. Guards of heavy gauge, PVC

(polyvinyl chloride) coated.

• Standard and reduced sound level models have

condensers fitted with single speed fans. Low sound

models have two speed fans fitted.

• The fan motors are the high efficiency, direct drive, 6

pole on standard sound models and 8 pole on reduced

and low sound models, 3 phase, Class-“F”, current

overload protected, totally enclosed (TEAO) type with

double sealed, permanently lubricated, ball bearings

• Fin and tube condenser coils of seamless, internally

enhanced, high condensing coefficient, corrosion re-

sistant copper tubes arranged in staggered rows and

mechanically bonded to corrosion resistant aluminum

alloy fins with full height fin collars. Design working

pressure is 450 PSIG (31 bar).

MICROPROCESSOR CONTROLS

• Microprocessor control system provides automatic

control of chiller operation including compressor start/

stop and load/unload, anti-recycle timers, condenser

fans, evaporator pump, evaporator heater, unit alarm

contacts and run signal contacts.

• Chiller automatically resets to normal chiller operation

after power failure.

• Unit operating software is stored in non-volatile

memory. Field programmed set points are retained

in lithium battery backed regulated time clock (RTC)

memory for minimum 5 years.

• Alarm contacts are provided to remote alert contacts

for any unit or system safety fault.

• Display and Keypad:

♦ 80 character liquid crystal display that is both view-

able in direct sunlight and has LED backlighting for

nighttime viewing. One keypad and display panel

is provided with every chiller.

♦ Display and keypad is accessible through display

access door without opening main control/electrical

cabinet doors.

♦ Display provides unit setpoints, status, electrical

data, temperature data, pressures, safety lock-

outs and diagnostics without the use of a coded

display.

♦ Descriptions in English (or available language op-

tions), numeric data in English (or Metric) units.

♦ Sealed keypad shall include unit On/Off switch.

• Programmable Setpoints (within Manufacturer limits):

display language; leaving chilled liquid temperature:

setpoint, control range; local or remote control; units of

measure; compressor lead/lag; and maximum chilled

water setpoint reset temperature range.

• Display Data: Chiller liquid return and leaving tempera-

tures, ambient, lead compressor identification, clock

Advertising