Accessories and options, Continued) – York UL R134A User Manual

Page 8

Advertising
background image

JOHNSON CONTROLS

8

Accessories and Options

(Continued)

.

BUILDING AUTOMATION SYSTEM INTERFACE:
• Chiller to accept 4 to 20mA or 0 to 10 VDC input to

reset the leaving chilled liquid temperature. (

Factory

Mounted)

MULTI-UNIT SEQUENCE CONTROL:

Separate sequencing control center provided to permit

control of up to eight chillers in parallel based of mixed

liquid temperature (interconnecting wiring by others).

(

Field Mounted)

VIBRATION ISOLATION:
• Neoprene Isolation
– Recommended for normal in-

stallations. Provides very good performance in most

applications for the least cost. (

Field mounted)

• 1” Spring Isolators – Level adjustable, spring and

cage type isolators for mounting under the unit base

rails. 1” nominal deflection may vary slightly by appli-

cation. (

Field mounted)

• 2” Seismic Spring Isolators – Restrained Spring-Flex

Mountings incorporate a rugged welded steel hous-

ing with vertical and horizontal limit stops. Housings

designed to withstand a minimum 1.0g accelerated

force in all directions to 2” (51mm). Level adjustable,

deflection may vary slightly by application. (

Field

mounted)

BUY AMERICAN ACT COMPLIANCE - In keeping with

the “Buy America Act”, products will be comprised of 50%

or more U.S. content and manufactured (final assembly)

in the U.S.A.

SERVICE ISOLATION VALVE – Service suction isola-

tion added to unit for each refrigerant circuit. (

Factory

Mounted)

CHICAGO CODE RELIEF VALVE - Special relief valves

per Chicago code. (

Factory Mounted)

PRESSURE RELIEF (CE/PED) SERVICE VALVE KIT

- Each relief valve is mounted on a sealable ball valve to

aid maintenance. (

Factory Mounted)

cooler, etc.), yet provides free air flow. This can cut

installation cost by eliminating the need for separate,

expensive fencing. (

Factory mounted)

• Louvered Panels (condenser coils only) – Painted

steel to match unit panels, louvered panels are

mounted over the exterior condenser coil faces on the

sides of the unit to visually screen and protect coils.

(

Factory mounted)

• Louvered Panels (full unit) – Painted steel to match

unit panels, to protect condenser coils from incidental

damage, visually screen internal components, and

prevent unauthorized access to internal components.

(

Factory mounted)

• Louvered (Condensers)/Wire Panels (Mechanical)

– Louvered steel panels on external condenser coil

faces, painted to match unit panels. Heavy gauge,

welded wire-mesh, coated to resist corrosion, around

base of machine to restrict unauthorized access. (

Fac-

tory Mounted)

EVAPORATOR OPTIONS:

1-1/2” Insulation – Double thickness insulation pro-

vided. (

Factory Mounted)

Raised Face Flange Accessory for cooler nozzles:

♦ 150 PSIG (10.3 bar), welded flanges (field kit,

matching pipe flange by contractor).

♦ 150 PSIG (10.3 bar) companion weld flanges. (field

kit - Not available with 460V units).

♦ 150 PSIG (10.3 bar), ANSI/AWWA C-606 COU-

PLINGS (field kit, matching pipe flange by contrac-

tor).

• Opposite Handed evaporator water connections

for ease of installation. Standard water connections

are on the left-hand side of the unit, when viewed from

the control panel end.

FLOW SWITCH ACCESSORY : Vapor proof SPDT, NEMA

3R switch, 150 PSIG (10.3 bar) DWP, 20°F to 250°F

(-28.9°C to 121.1°C) with 1” NPT (IPS) connection for

upright mounting in horizontal pipe (This flow switch or

equivalent must be furnished with each unit). (

Field

Mounted).

DIFFERENTIAL PRESSURE SWITCH - Alternative to the

paddle-type flow switch. 3-45 PSIG (0.2-3 bar) range with

1/4" NPTE pressure connections. (

Field Mounted)