Accessories and options – York UL R134A User Manual

Page 7

Advertising
background image

JOHNSON CONTROLS

FORM 201.23-EG1 (1007)

7

Accessories and Options

SOUND REDUCTION OPTIONS – The standard chiller

has fans that operate at normal speed, no compressor

enclosure, and is typically used in non-sensitive sound

areas such as industrial areas or locations with loud traffic

background noise. One or more of the following sound re-

duction options may be employed by the system designer

as normally generated machine noise is considered in the

overall project design.

Ultra Quiet Fans (Factory Mounted) – With this option,

the basic chiller is equipped with specially designed fans

and motors to provide lower sound levels and retain ap-

propriate airflow. The result is reduced fan generated

noise with no adverse effect on the chiller capacity or

efficiency performance.

Two-Speed Fans (Factory Mounted) – With this option,

the basic chiller is equipped with fans designed with two

operating speeds. At high ambient conditions the fans

operate at the normal speed with sound levels equivalent

to Ultra Quiet Fans. As the ambient temperature falls the

fans automatically reduce to slow speed reducing sound

levels. If very low sound is required at all ambient condi-

tions normal fan speed can be inhibited.

Reduced Sound Option (Factory Mounted) – With this

option the chiller is equipped with an unlined compres-

sor enclosure. This option is typically used for daytime

operation where background noise is lower than normal

city traffic etc.

Low Sound Option (Factory Mounted) – This option

is only available with the selection of Ultra Quiet Fans or

Two-Speed Fans. The chiller is equipped with an acousti-

cally lined compressor enclosure. This option is typically

for locations near residential areas, hotels, or hospitals

etc where background noise is limited. When paired with

the Two-Speed Fan option the unit can operate at normal

speed during the day, when background noise levels are

noticeable, and at low speed in the evening and at night

when background levels are lower.

SilentNight™ - Standard variable speed compressors

result in a chiller system that has lower part load sound

values than conventional air-cooled chillers. Over 99%

of chiller operating hours occur when building loads are

less than design and/or ambient temperatures are less

than design. As a result, all YCIV model chillers will

operate with less than full load sound output nearly all

the time – this is especially important on evenings and

weekends when neighbors are home the most. Due to

time of day based sound regulations it may be desirable

to force the chiller to a lower sound level on demand.

The SilentNight™ control option provides a control input

to limit sound output of the chiller based on time of day.

This feature is programmable at the chiller panel or can

be controlled remotely via signal (4-20mA or 0-10 VDC)

from a BAS system.

CIRCUIT BREAKER – Power panel will come equipped

with a factory mounted circuit breaker at point of incom-

ing single or multi-point connection that provides the

following:
• Means to disconnect power mounted on chiller.
• Circuit breaker sized to provide the motor branch

circuit protection, short circuit protection and ground

fault protection for the motor branch-circuit conductors,

the motor control apparatus and the motors. (Chiller

mounted circuit breaker option sized for branch circuit

protection eliminates the need to provide a separate

‘line of sight’ disconnect and separate branch circuit

protection device.)

• Lockable operating handle that extends through power

panel door so that power may be disconnected without

opening any panel doors.

• Short Circuit Withstand Rating of the chiller electrical

enclosure when using circuit breaker option is 380,

400, & 460V: 65,000 Amps. Rating IAW UL508.

CONDENSER COIL PROTECTION – Standard con-

denser coil construction materials include aluminum fins,

copper tubes, and galvanized tube supports for generally

good corrosion resistance. However, these materials are

not adequate for all environments. The system designer

can take steps to inhibit coil corrosion in harsh applica-

tions and enhance equipment life by choosing from these

options based on project design parameters and related

environmental factors. (

Factory Mounted)

• PRE-COATED FIN CONDENSER COILS – The air

cooled condenser coils are constructed of epoxy-

coated aluminum fins. This can provide corrosion

resistance comparable to copper-fin coils in typical

seashore locations. Either these or the post coated

coils (below), are recommended for units being in-

stalled at the seashore or where salt spray may hit

the unit.

• POST-COATED EPOXY DIPPED CONDENSER

COILS – The unit is built with dipped-cured epoxy

condenser coils. This is another choice for seashore

and other corrosive applications (with the exception

of strong alkalies, oxidizers and wet bromine, chlo-

rine and fluorine in concentrations greater than 100

ppm).

• COPPER FIN CONDENSER COILS – The unit con-

structed with copper tube condenser coils, which have

copper fins. (This is not recommended for units in

areas where they may be exposed to acid rain.)

PROTECTIVE CHILLER PANELS:
• Wire Panels (full unit)
– UV stabilized black polyvi-

nyl chloride coated, heavy gauge, welded wire mesh

guards mounted on the exterior of the unit. Protects

condenser coil faces and prevents unauthorized ac-

cess to refrigerant components (compressors, pipes,