Dimensions, Si - continued – York UL R134A User Manual

Page 100

Advertising
background image

JOHNSON CONTROLS

100

Dimensions –

SI - continued

Notes:

1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,

reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-

dictable air patters and possible diminished performance. Johnson Controls’ unit controls will optimize the operation without nuisance

high pressure safety cutouts; however, the system designer MUST consider potential performance degradation.

Access to the unit control center stipulates the unit is no higher than on spring isolators. Recommended minimum clearances: side to wall

- 2m; rear to wall - 2m; control panel end to wall - 1.2m; top - no obstructions whatsoever; distance between adjacent units - 10’. No more

than one adjacent wall may be higher than the unit.

YCIV1220E/V and YCIV1340S/P

VIEW C-C

VIEW B-B

305

CONTROL ENTRY

76 WIDE X 343 HIGH

38

102

POWER ENTRY

254 WIDE X 330 HIGH

44

POWER ENTRY IS ON BOTTOM OF PANEL

2238

VIEW A-A

C

B

B

C

Advertising