VEGAMET 614V

Settings in the „Reduced menu“

6.3 Adjustment with medium

You can either carry out the adjustment

with

medium or

without

medium. Adjustment with

medium means that you carry out the adjust-
ment taking the actual level into account. To
carry out an adjustment with medium, it is
necessary to know the percentage value of
the actual vessel filling.

In this procedure, the percentage values
which correspond to the actual min. and max.
fillings are entered. It doesn’t matter if you
enter first the min. value or the max. value. If
you know, for example, that your filling is
actually 80 %, you can enter in the menu
“max. adjustment” the value „80“. Later, when
your filling is, for example, 10 %, you enter in
the menu “min. adjustment” the value „10“.

The bigger the difference between the two
adjustment points, the more precise the
measurement over the whole measuring
curve. An adjustment at 0 % and 100 %
would be ideal. For practical reasons, it is not
always possible to completely empty or fill a
vessel. The distance between the two adjust-
ment points, however, should be at least
10 % of the sensor range.

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Ad-
just-
ment

with
medium

Min-
adjust
at %

0,0

Max-
adjust
at %

100,0

6.2 Sensor optimization

Like the measurement loop name, the sensor
name can also be modified if you want to give
it another designation. To do this, move to the
menu item „Sensor-Tag…“ (first menu item in
the sensor menu). The procedure is the
same as the modification of the measurement
loop name. The sensor name is saved in the
memory component of the sensor.

When you move to the menu item „Sensor
menu“, a new menu item opens which is
independent of VEGAMET. It is provided by
the connected sensor and has different ad-
justment options (e.g. installation geometry,
meas. environment…) depending on the
sensor type. The appropriate description is
stated in the operating instructions manual of
the sensor. These data, like the sensor name,
are also saved in the sensor. If at a later date
the sensor is connected to another signal
conditioning instrument, its adjustment data
remain.

Normally, the sensor will have been adapted
to customer-specific conditions so that modi-
fications in the sensor menu will only be nec-
essary if the sensor is used for a
measurement other than originally planned.

TAG-
No. 1
%
xx,x

Param.

TAG-
No. 1

Confi-
gura-
tion

Sensor
opti-
mize

Sensor
type

Hydro-
static

For radar/ultrasonic sensors: see

MINICOM menu schematic in the

VEGASON/VEGAPULS operating

instruction manual in chapter „Adjust-

ment with VEGAMET or MINICOM“.