Error code

Meaning

Diagnosis

E051

Failure during transmission of measured values via DISBUS. It is not possible
to receive a valid measured value via DISBUS from the remote VEGAMET; the
communication with the remote VEGAMET, however, is okay.
Reason:
- failure on remote VEGAMET
- the input on the remote VEGAMET which should be transmitted is not yet
configured

E052

The input number of the VEGAMET from which a measured value is expected
has not yet been assigned.

E060

Span of the current output values too small. The values for the current output
are too close together or are identical. Please check the adjustment of the
current output.

E061

Span of the voltage output values too small. The values for the voltage output
are too close together or are identical. Please check the adjustment of the
voltage output.

E063

Incorrect sensor characteristics values. Please check the sensor characteris-
tics values

E102

A reset of the configuration was carried out on this VEGAMET via the key-
board.

E110

Switching hysteresis too small. The switching points are too close together or
are identical.

E111

Relay switching points swapped. The relay switching points are reversed with
respect to the selected relay mode.