VEGAMET 614V

Product description

1.4 Technical data

Power supply

Operating voltage / power consumption

U

nom

= 90 … 250 V AC, 50/60 Hz / approx. 14

VA

= 90 … 250 V DC

Optional instrument version

U

nom

= 20 … 72 V DC / 7 W
= 20 … 53 V AC, 50/60 Hz, 14 VA

Power supply with Ex approved instrument

Operating voltage / power consumption

U

nom

= 20 … 250 V AC, 50/60 Hz / 14 VA
= 20 … 72 V DC / 5 W

Meas. data input

Number

1 input

Type of input

active two-wire input, digital (VBUS) (sensor
powered by VEGAMET)

Sensor

pressure transmitters, ultrasonic sensors and
radar sensors

Voltage

approx. 25 V DC

Power limitation

at approx. 4.5 W, short-circuit proof

Min. adjustment delta

2 % of sensor range (hydrostatic)
5 mm (ultrasonic, radar)

Connection cable

2-wire standard cable (screening
recommended)

max. cable length

1000 m

max. resistance per wire

15

Meas. data input with Ex approved instrument

Voltage

approx. 15 V at 5 mA
approx. 13.5 V at 25 mA

Current limitation

at 32 mA (short-circuit proof)

further data of the meas. data input the same as the instrument without Ex approval

Current output

Number

2 outputs

Function

analogue output of the processing results

Range

individually adjustable in the range of 0 … 20 mA

Load

max. 500

Resolution

1 µA

Linearity error

0.05 % (relating to 20 mA)

Temperature error

0.05 %/10 K (relating to 20 mA)

Voltage output

Number

2 outputs

Function

analogue output of the processing results

Range

individually adjustable in the range of 0 … 10 V

Current

max. 1 mA

Resolution

0.5 mV

Linearity error

0.05 % (relating to 10 V)

Temperature error

0.06 %/10 K (relating to 10 V)