VEGA VEGAMET 614V User Manual

Page 8

Advertising
background image

8

VEGAMET 614V

Product description

Electrical protective measures

Instrument

IP 30

Plug-in socket

IP 20

Protection class

II

Overvoltage category

II

Electrical separating measures

Reliable separation acc. to
VDE 0106, part 1 between

power supply, fail safe and level relay
and meas. data inputs

- reference voltage

250 V

- insulation resistance

2.3 kV

Galvanic separation

between relay outputs

- reference voltage

250 V

- insulation resistance

1.4 kV

Potential separation

between DISBUS and outputs

- reference voltage

50 V

- insulation resistance

0.5 kV

Common reference potential at

voltage and current output

Mechanical data

Series

module unit with plug-in socket, incl. transpa-
rent cover, sensor terminal cover, coded
pin, two connection jumpers

Mounting

carrier rail mounting acc. to DIN 46 277, Bl. 3

Dimensions, unmounted

W = 72 mm, H = 118.5 mm, D = 134 mm

Weight

approx. 480 g

CE conformity

The VEGAMET 614V Ex signal conditioning instrument meets the protective regulations of
EMC (89/336/EWG) and NSR (73/23/EWG). Only for use in industrial areas. Conformity has
been judged acc. to the following standards:
EMC

Emission

EN 50 081 - 2: 1993

Susceptibility

EN 50 082 - 2: 1995

NSR

EN 61 010 - 1: 1993

Advertising