5 dimensions, Ex technical data, Power supply operating voltage u – VEGA VEGAMET 614V User Manual

Page 9: 2 v - current i, 270 ma - power p, Negligible effective inner capacitance c, 28 mh max. permissible outer capacitance c, Product description

Advertising
background image

VEGAMET 614V

9

1

2

3

4

9

10

11

12

17 18

20 21 22

134

54,5

72

5

6

7

8

13 14

15 16

23 24 25 26 27 28

118,5

Ser. No.
12345678

CONNECT

614

%

100

+

-

OK

ESC

on

1

2

Transparent cover

Carrier rail 35 x 7.5 or 35 x 15 acc.
to EN 50 022

Ex technical data

Power supply

Operating voltage

U

nom

= 20 … 250 V AC
= 20 … 72 V DC

Reference voltage

U

m

= 253 V AC or 125 V DC

Meas. data input (intrinsically safe circuit)

Classification

II (1) G [EEx ia] II C

Max. values
- voltage

U

o

= 18.2 V

- current

I

o

= 270 mA

- power

P

o

= 926 mW

Characteristics

linear

Effective inner inductance L

I

negligible

Effective inner capacitance C

I

negligible

EEx ia IIC

Max. permissible outer inductance L

O

0.28 mH

Max. permissible outer capacitance C

O

297 nF

The intrinsically safe circuits is reliably separated from the non-intrinsically safe circuits up
to a peak value of the nominal voltage of 375 V. The max. voltage on the non-intrinsically
safe circuits must not exceed 253 V

eff

in case of failure.