4 configuration of outputs, Settings in the „extended menu – VEGA VEGAMET 614V User Manual

Page 29

Advertising
background image

VEGAMET 614V

29

Settings in the „Extended menu“

7.4 Configuration of outputs

PC/DCS output and DIS output:

The PC/DCS signal as well as the DIS signal
are transmitted via the DISBUS. The PC/DCS
output delivers output signals from
VEGAMET to the interface converter
VEGACOM 557. This interface converter
transfers the signals from VEGAMET via
different standard protocols to connected
systems (DCS/DCS). In the menu items „DCS
1 to“ up to „DCS 7 to…“ the measurement
loop can be assigned or switched off. In the
menu items „PC/DCS relay status“ and „PC/
DCS input status“ it can be specified that the
relay mode is transmitted via the DISBUS. Up
to seven external indicating instruments
(VEGADIS 174) can be connected to
DISBUS. In the menu items „DIS 1 to…“ up to
„DIS 7 to–“ the measurement loop can be
coordinated or switched off.

The current, volt and relay outputs with
number 1 (current 1, Volt 1 and Rel. 1) are
assigned as factory setting to measurement
loop „TAG-No. 1“. If a second measurement
loop exists, as is the case when a sensor
with temperature output is connected, then
the outputs with number 2 are assigned to
measurement loop TAG-No. 2. All outputs can
be assigned individually to the other meas-
urement loop or switched off (----), i.e. the
switched off outputs do not access a meas-
urement loop.
A hold function or a reset of alarm functions
can be assigned to each operating relay. In
this case, the menu item „Input“ appears.
Here, the relay can be assigned to „Input 4“
(correction input). For a description of the
relay functions, see the following pages.

TAG 2
----

Config
inputs

Config
meas.
loop

Config
outputs

Config
current
output

Current
1 to

TAG -
No. 1

Current
2 to

TAG -
No. 2

Config
Volt
output

Config
relay
output

Config
PC/
DCS-
output

Config
VEGA-
DIS

DIS 1
to

TAG -
No. 1

DIS 7
to

----

PC/
DCS
meas.
values

DCS 1
to

TAG -
No. 1

DCS 7
to

----

PC/DCS
relay
status

off

PC/DCS
input
status

off

Confi-
gura-
tion

Param.
TAG-
No. 2

Fail
safe
relay

Rely

Stan-
dard

Ope-
rating
relay

Rel. 1
to

TAG -
No. 1

Rel. 2
to

TAG -
No. 2

TAG 1
----

TAG 2
----

TAG 1
----

----

----

TAG 2
----

Volt1
to

TAG -
No. 1

Volt2
to

TAG -
No. 2

TAG 1
----

TAG -
No. 1
%
xx,x

Param.
TAG-
No. 1

Advertising