Relay outputs, Settings in the „extended menu – VEGA VEGAMET 614V User Manual

Page 33

Advertising
background image

VEGAMET 614V

33

Settings in the „Extended menu“

Relay outputs

In the menu item „

prop. to

“, you choose a

parameter that the relay will react to. You can
choose between percent and volume („prop.
to volume“ is useful when under „Conditioning
- Linearisation curves“, for example a spheri-
cal tank or a user-programmable lin. curve is
selected). In the next menu item you can
select the suitable

Unit

. In the menu item

Mode

“ the mode of the relay can be se-

lected. The individual relay modes are de-
scribed on the following pages.

If mode „Tendency rising“ or „Tendency fall-
ing“ is selected, the menu items „Deviation“,
„Dev. per time“, „Cycle time“ and „Number of
cycles“ appear.

With all other modes, the menu items „Low“
and „High“ appear. There you can determine
the switching points for the relay.
The menu item „

Failure mode

“ always ap-

pears. „Failure mode off“ causes the relay to
deenergise when a failure (e.g. sensor
shortcircuit) occurs. „Failure mode hold“
causes the actual relay status to be main-
tained when a failure occurs.

Under „Add’l functions“ you can adjust a
switch on delay (t on) and a switch off delay
(t off) of the relay of max. 600 s (with the relay
modes „Tendency rising“ or „Tendency fall-
ing“, no switching delay can be set).

Param.
TAG-
No. 2

like TAG-No. 1

Param.
TAG-
No. 1

TAG -
No. 1
%
xx,x

Adjust-
ment

Signal
condi-
tioning

Out-
puts

Cur-
rent
out-
puts

Volt
outputs

Relay
outputs

Relay
output
1

Relay
output
2

prop.
to

Per-
cent

Unit

0,0%

Mode

Over-
fill
protec

Low

%

0,0

Failure
mode

off

Add’l
func-
tions

Cycle
time
s

1

Number
of
cycles

10

like relay output 1

High

%

100,0

Devia-
tion
s

1,0

De-
viation
per
time

Switch-
ing
delay

t off

s

0

Volume
Height
Pressure

Dry run protec.
Switching window on
Switching window off
Tendency rising
Tendency falling

0,00 %
Tare %

hold

t on

s

0