7 outputs – VEGA VEGAMET 614V User Manual

Page 24

Advertising
background image

24

VEGAMET 614V

6.7 Outputs

Overfill protection

The relay of relay output 1 deenergises at the
switching point „Low“ (safe switching condi-
tion).

The relay of relay output 1 deenergises at the
switching point „High“ (safe switching condi-
tion).

Dry run protection

The current output of VEGAMET is set to
4 … 20 mA. By pushing [+] or [–] and [OK]
you can set the output to the following values:
0/20 mA, 20/4 mA and 20/0 mA.

Beside the preadjustment (0/10 V), the follow-
ing options are available for the voltage out-
put: 10/2 V, 10/0 V and 2/10 V.

As a factory setting, the relay outputs are set
to mode „Overfill protection“ (mode A). By
pushing [+] or [–] and [OK] you can assign
the mode „Dry run protection“ (mode B)
separately for each relay output. In the next
menu items you can determine the upper and
lower switching points for the set mode.
The graphics on the right show the behaviour
of the relay outputs and LEDs depending on
the level.

Settings in the „Reduced menu“

t

Relay output

Parameter

High

Low

t

High

Low

Parameter

Relay output

Meas.
value
indication

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Ad-
just-
ment

Signal
condi-
tioning

Out-
puts

Current
output 1

4/20mA

Volt
output
1

0/10V

Relay
output
1

Mode

Over-
fill
protec

Low

%

0,0

Relay
output
2

High

%

100,0

Mode

Over-
fill
protec

Low

%

0,0

High

%

100,0

0/20mA
20/4mA
20/0mA

10/2V
10/0V
2/10V

Dry run
protec

Dry run
protec

Volt
output
2

0/10V

10/2V
10/0V
2/10V

Current
output 2

4/20mA

0/20mA
20/4mA
20/0mA

Advertising