6.5 Scaling

Settings in the „Reduced menu“

The adjustments under scaling determine
which number values and which unit will be
actually displayed on the measured value
indication (upper menu item). In the menu
items „0 % corresponds…“ and „100 % cor-
responds…“ you can enter with [+] or [–]
and [OK] values which should be displayed
at 0 % and at 100 % filling. In the menu item
„Decimal point…“ you determine the position
of the decimal point. In the next menu item
„prop. to…“ you can select from a list of pa-
rameters: percent, mass, volume, pressure
etc. After pushing [+] or [–] save with [OK].
According to this adjustment, the menu item
„Unit…“ provides a new choice, e.g. m, dm,
cm, mm, ft, yd and in, if you have selected
the parameter „Height“ (compare chapter „8
Measured quantity and units“).

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Ad-
just-
ment

Sig-
nal
condi-
tioning

Scal-
ing

Integr
ation
time s

0

Unit

– –

prop.
to

unde-
fined

Deci-
mal
point

888,8

100%
corres-
ponds

1000

0%
corres-
ponds

0

Meas.
value
indication

Adjustment example

You know the data of the vessel, i.e. you
know that at 0 % filling, the distance from the
liquid to the sensor is 3.5 m and at 100 %
filling, 0.3 m.

In this menu item, you choose the
adjustment unit, e.g. m (d), if you use
a radar sensor [m (d) = distance in
m]. Use the [+] and [–] key to

choose the unit and [OK] to save the se-
lected unit.

Enter in these two menu items the
distance values (d1 and d2). With the
[+] and [–] keys you set the values,
with [OK] you save them.

Note that in this example, a lower
distance value exists at 100 % filling
than with 0 % filling!

Adjust-
ment

m(d)

0%
at

m (d)

3,50

100%
at

m (d)

0,30

3.5 m at 0 %

0.3 m
at 100 %

d1

d2

Radar sensor