VEGA VEGAMET 614V User Manual

Page 7

Advertising
background image

VEGAMET 614V

7

Product description

Relay outputs

Number

2 operating relays, 1 fail safe relay

Contact

floating spdt

Contact material

AGSNO

2

, hard gold plated

Turn-on voltage

min. 10 mV DC
max. 250 V AC/DC

Switching current

min. 10 µA
max. 3 A AC, 1 A DC

Turn-on voltage

max. 750 VA
max. 18 W at U > 40 V DC
max. 40 W at U

40 V DC

Min. switching hysteresis
(Low/High delta)

0.5 %

DISBUS output

Function

digital transmission for linking between signal

conditioning instruments and for connecting
digital indicating instruments

Connection cable

2-wire standard cable (screening
recommended)

max. cable length

1000 m

max. resistance per wire

15

Indicating elements

Clear text indication

LC display
- 4-lines, 6 digits each
- background lighting

Analogue indication

LED chain consisting of:
- 11 segments 0 % … 100 %
- indicates the actual value of the selected

measurement loop

LEDs in front plate

green: operating voltage on
red: fault signal (LED lights with deenergised
relay)
yellow: relay switching condition (standard
adjustment: LED lights with energised relay)

Adjustment elements

Front plate

6 keys for configuration and parameter setting

Upper housing side

rotary switch for adjustment of the instrument
address
on DISBUS (in mounted status covered by
plug-in socket)

Ambient conditions

Permissible ambient temperature

-20°C … +60°C

Storage and transport temperature

-40°C … +80°C

Electrical connection

Screw terminal

max. 1.5 mm

2