5 adjustment – VEGA VEGAMET 614V User Manual

Page 30

Advertising
background image

30

VEGAMET 614V

Settings in the „Extended menu“

7.5 Adjustment

The

adjustment with medium

corresponds

to the procedure in the reduced menu (see
appropriate chapter).

- if the medium is changed later on (medium

with another density value) and no new
adjustment can be made
or

- if the MET indication and the DIS outputs

relate to height in meters

note the following:
In applications with hydrostatic pressure
transmitters, the adjusted density value (see
menu „Parameter“) must correspond to the
value of the medium.

For the

adjustment without medium,

two

anticipated values for level, pressure etc.
corresponding to 0 % and 100 % must be
entered.

The menu item „Offset correction“ is activated
when hydrostatic pressure transmitters are
connected. The offset correction should be
carried out after installation of the sensor, as
the sensor values can differ slightly due to
different installation positions or strong tight-
ening during mounting.
With the offset correction, the meas. data of
the unpressurised sensor (vessel empty) are
detected as correction values and taken into
account in all subsequent measurements.

Param.
TAG-
No. 1

Adjust-
ment

with
medium

without
medium

Min-
adjust
at %

0,0

Max-
adjust
at %

100,0

Adjust-
ment

bar

Offset
correc-
tion

0%
at

bar

0,000

100%
at

bar

5,000

Sensor
unpres-
sur’d?
OK ?

Offset
corr.
Now !
OK ?

TAG -
No. 1
%
xx,x

Param.
TAG-
No. 2

like TAG-No. 1

Advertising