2 configuration of meas. systems, Meas. systems with vegason 51k … 53k – VEGA VEGASON 51K…53K User Manual

Page 10

Advertising
background image

10

VEGASON 51K … 53K

2

4 … 20 mA

-

+

1)

4

2.2 Configuration of meas. systems

A meas. system consists of a sensor with a
4 … 20 mA signal output and a unit evaluat-
ing or processing the level proportional cur-
rent signal.

On the following pages you will see the in-
strument configurations called meas. system
which are shown in the following partly with a
signal processing.

Meas. systems in two-wire technology:

• 4 … 20 mA drawing without processing

unit,

(bottom)

• 4 … 20 mA on active DCS,

(page 12)

• 4 … 20 mA on active DCS (Ex-area),

(page 13)

• 4 … 20 mA on passive DCS,

(page 14)

• 4 … 20 mA on indicating instrument

VEGADIS 371 Ex,

(page 15)

Meas. systems in four-wire technology:

• 4 … 20 mA drawing without signal condi-

tioning instrument, (page

16)

VEGADIS 50

VEGA-
CONNECT 2

HART

®

-hand-

held

Types and versions

Meas. systems with VEGASON 51K … 53K

• Two-wire technology (loop powered), supply and output signal via a two-wire line
• Output signal 4 … 20 mA (passive)
• Optional external indicating instrument with analogue and digital indication (can be mounted

up to 25 m away from the sensor)

• Adjustment with PC, HART

®

-handheld or adjustment module MINICOM (can be plugged into

the sensor or in the external indicating instrument VEGADIS 50)

1)

If the resistors of the processing
systems connected to the
4 … 20 mA-signal output are less
than 200

, a resistor of 250

to

350

must be connected to the

connection line during adjustment.

The digital adjustment signal would
be extremely damped or short-
circuited via too small input
resistors of the connected
processing system which means
that the digital communication with
the PC could no longer be
ensured.