5 flow measurement, Rectangular flume, Khafagi-venturi flume – VEGA VEGASON 51K…53K User Manual

Page 30

Advertising
background image

30

VEGASON 51K … 53K

B

Khafagi-Venturi flume

90°

h

max

Sensor

3 … 4 x h

max

Flow measurement on open flumes

h

max

2 x h

max

Overfall edge

90°

Flow measurement on open flumes

Upstream water

Downstream water

5 cm

90°

3 … 4 x h

max

Overfall edge

Mounting and installation

4.5 Flow measurement

The short examples on this page only give
introductory information for your flow meas-
urement. Planning information is given by the
flume manufacturers and in special literature.

Rectangular flume

- Installation of the sensor on the upstream

side

- Note distance to the overfall edge

(3 … 4 x h

max

)

- Installation centered to the flume
- Edge opening

2 x h

max

from ground

- Installation perpendicular to the liquid sur-

face

- Keep min. distance relating to h

max

- Min. distance of the edge opening of down-

stream water

50 mm

Khafagi-Venturi flume

- Installation of the sensor on the inlet side
- Note distance to the Khafagi-Venturi flume

(3 … 4 x h

max

)

- Installation perpendicular to the liquid sur-

face

- Keep min. distance relating to the height of

damming h

max

max.

distance

Advertising