The most important adjustment steps – VEGA VEGASON 51K…53K User Manual

Page 47

Advertising
background image

VEGASON 51K … 53K

47

Set-up

VEGALOG

VEGAMET

Rx

The most important adjustment steps

On the following pages you see a menu plan
for the HART

®

-handheld in conjunction with

VEGASON 51K … 53K sensors. The most
important adjustment steps are marked in the
menu plan with the letters A … E. When enter-
ing parameters first of all the key "

ENTER“

must be pressed. The adjustment is thereby
saved in the handheld, but not in the sensor
itself.

After pressing "

SEND“, a warning is dis-

played, which informs you that you are about
to modify the configuration and for that,
safety reasons, you should switch your sys-
tem over to manual operation.

After having pressed "

ENTER“, press "SEND“

(here in the example for the min.-adjustment).

Press "

OK“ and the adjustment will now be

transferred to the sensor. After a short time
you are asked to switch you system over
from manual to automatic operation. Confirm
with "

OK“.

4.2
(5.2)

Generic: SENSOR

1 PV LRV

5.850 m

2 PV URV

0.300 m

HELP SEND HOME

Generic: SENSOR
PV URV

5.850 m

0.300

m

HELP DEL

ESC ENTER

Generic: SENSOR
WARN-Loop should be
removed from
automatic control

ABORT OK

Generic: SENSOR
NOTE- Loop may be re-
turned to automatic control

OK

Generic: SENSOR

1 PV LRV

5.850 m

2 PV URV

0.300 m

HELP

HOME

You see the actual carried out adjustment.