Mounting and installation

4.7 Installation error

Foam generation

Strong foam on the product can cause faulty
measurements. Provide measures to avoid
foam, measure in a bypass pipe or use an-
other meas. principle, e.g. capacitive electro-
des or hydrostatic pressure transmitters.

Foam generation

;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;

Direct sensor vertically to the product surface

Wrong directing to the product

Weak measuring signals are caused if the
sensor is not directed to the product surface.
Direct the sensor axis vertically to the prod-
uct surface to achieve optimum measuring
results.

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

;;;;

Strong heat fluctuations

Strong heat fluctuations, e.g. due to the sun
cause measuring errors. Provide a shield.

Min. distance to the medium

When the min. distance to the medium is not
maintained, the instruments show wrong
measured values. Mount the instruments with
the required min. distance.

Sensor too close to the vessel wall

Correct

Wrong

Strong heat fluctuations