5

Connecting to power supply and bus
system

5

.1 Preparing the connection

Always keep in mind the following safety instructions:

l

Connect only in the complete absence of line voltage

l

If voltage surges are expected, install overvoltage arresters

The instrument requires an operating voltage of 8 … 30 V DC.
Operating voltage and digital bus signal are carried on separate two-
wire connection cables.

The instrument is connected with standard two-wire, twisted cable
suitable for RS 485. If electromagnetic interference is expected which
is above the test values of EN 61326 for industrial areas, screened
cable should be used.

Use cable with round cross-section. A cable outer diameter of 5 … 9 mm
(0.2 … 0.35 in) ensures the seal effect of the cable gland. If you are
using cable with a different diameter or cross-section, exchange the
seal or use a suitable cable gland.

Make sure that the entire installation is carried out according to the
Fieldbus specification. In particular, make sure that the bus is
terminated with suitable terminating resistors.

With plastic housing, the NPT cable gland or the Conduit steel tube
must be screwed without grease into the threaded insert.

Max. torque for all housings see chapter "Technical data"

With systems with potential equalisation, connect the cable screen
directly to ground potential at the power supply unit, in the connection
box and at the sensor. The screen in the sensor must be connected
directly to the internal ground terminal. The ground terminal outside on
the housing must be connected to the potential equalisation (low
impedance).

In systems without potential equalisation, connect the cable screen
directly to ground potential at the power supply unit and at the sensor.
In the connection box or T-distributor, the screen of the short stub to
the sensor must not be connected to ground potential or to another
cable screen. The cable screens to the power supply unit and to the
next distributor must be connected to each other and also connected
to ground potential via a ceramic capacitor (e.g. 1 nF, 1500 V). The low
frequency potential equalisation currents are thus suppressed, but the
protective effect against high frequency interference signals remains.

Safety instructions

Voltage supply

Connection cable

Cable gland ½ NPT

Cable screening and
grounding

VEGAPULS

62 • Approval according to LPR radio standard

25

5 Connecting to power supply and bus system

41722

-EN