VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol Approval according to LPR radio standard User Manual

Page 62

Advertising
background image

Input variable

Measured variable

The measured quantity is the distance between
process fitting of the sensor and product surface.
The reference plane is the seal surface on the
hexagon or the lower side of the flange.

3

4

2

1

Fig. 43: Data of the input variable

1

Reference plane

2

Measured variable, max. measuring range

3

Antenna length

4

Useful measuring range

Max. measuring range

35 m (114.83 ft)

Output variable

Output

-

Physical layer

Digital output signal according to standard EIA-485

-

Bus specifications

Modbus Application Protocol V1.1b, Modbus over
serial line V1.02

-

Protocols

Modbus RTU, Modbus ASCII, Levelmaster

Max. transmission rate

9.6 Kbit/s

Accuracy (according to DIN EN 60770-1)

Process reference conditions according to DIN EN 61298-1

-

Temperature

+

18 … +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions

-

Min. distance to installations

>

200 mm (7.874 in)

-

Reflector

Corner reflector

62

VEGAPULS

62 • Approval according to LPR radio standard

10 Supplement

41722

-EN

-120706