Scadapack wiring plan, Parameter – VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol Approval according to LPR radio standard User Manual

Page 87

Advertising
background image

ScadaPack

Wiring plan

+

+

power supply

MODBUS

D0

D1

IS GND

USB

1

3

2

1

3

4

5

5

2

1

3

4

9

6

7

8

2

of

f

on

( )

( )

(-)

(-)

+8

+30 Vdc

to

GND

COM Part 3 (C3)
RS485

TXD-
TXD+
GND

Fig. 50: Connection of VEGAPULS 62 to RTU ScadaPack

1

VEGAPULS 62

2

RTU ScadaPack

3

Voltage supply

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

Floating Point

Input Register Base Number

30001

The basic number of the input registers is always added to the input register address of VEGAPULS
62.

Address 31303 must hence be entered as register address for 1302 for RTU ScadaPack.

VEGAPULS

62 • Approval according to LPR radio standard

87

10 Supplement

41722

-EN

-120706

Advertising