Text mes-
sage

Cause

Rectification

C

700

Simulation

l Simulation active

l Finish simulation
l Wait for the automatic end

after 60 mins.

The following table shows the error codes and text messages in the
status message "Out of specification" and provides information on
causes as well as corrective measures.

Code
Text mes-
sage

Cause

Rectification

S

600

Unpermissible
electronics
temperature

l Temperature of the elect-

ronics in the non-specified
section

l Check ambient temperatu-

re

l Isolate electronics
l Use instrument with higher

temperature range

S

601

Overfilling

l Danger of vessel overfilling l Make sure that there is no

further filling

l Check level in the vessel

The following table shows the error codes and text messages in the
status message "Maintenance" and provides information on causes as
well as corrective measures.

Code
Text mes-
sage

Cause

Rectification

M

500

Error with the
reset delivery
status

l With the reset to delivery

status, the data could not
be restored

l Repeat reset
l Load XML file with sensor

data into the sensor

M

501

Error in the
non-active li-
nearization
table

l Hardware error EEPROM

l Exchanging the electronics
l Send instrument for repair

M

502

Error in the
diagnosis me-
mory

l Hardware error EEPROM

l Exchanging the electronics
l Send instrument for repair

Out of specification

Maintenance

VEGAPULS

62 • Approval according to LPR radio standard

53

8 Diagnosis, Asset Management and service

41722

-EN

-120706