VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol Approval according to LPR radio standard User Manual

Page 39

Advertising
background image

5

Save settings with [OK]

The respective min. and max. measured value is saved in the sensor.
The values are displayed in the menu item "Peak values".

When non-contact level sensors are used, the measurement can be
influenced by the respective process conditions. In this menu item, the
measurement reliability of the level echo is displayed as dB value. The
measurement reliability equals signal strength minus noise. The higher
the value, the more reliable the measurement. With a functioning
measurement, the values are > 10 dB.

The "Echo curve" shows the signal strength of the echoes over the
measuring range in dB. The signal strength enables an evaluation of
the quality of the measurement.

The "False signal suppression" displays the saved false echoes (see
menu "Additional settings") of the empty vessel with signal strength in
"

dB" over the measuring range.

Diagnosis/Peak value

Diagnosis/Measurement
reliability

Diagnoses/Curve indica-
tion

VEGAPULS

62 • Approval according to LPR radio standard

39

6 Set up the sensor with the indicating and adjustment module

41722

-EN

-120706

Advertising