R&M Materials Handling VARIABLE SPEED CONTROLS ControlMaster NXT Service Manual User Manual

Page 19

Advertising
background image

R&M Materials Handling, Inc.

4501 Gateway Boulevard

Springfield, Ohio 45502

P.: (937) 328-5100

FAX: (937) 325-5319

19/53

R&M Materials Handling, Inc. reserves the right to alter or amend the above information without notice.

The bridge travelling motor installed at the opposite end from the bridge panel.

The bridge travelling motor installed at the bridge panel end of the main girder.

The frequency converter.

If the European regulations for EMC are not adhered to, both motor cables can be 40 m long.

Exception: 003 with two motors (MF06MA200)

Model 003 with two motors shall be connected as illustrated in the following picture. The grounding cables of the
motors shall be connected to the grounding terminals of the converter. The ferrite component shall be placed on
the wires between the frequency converter and the terminal blocks, near the converter. The phase and grounding
wires shall go through the ferrite component twice.

Advertising