5.2.5 S7 Current Limit in traveling movement application

The frequency converter limits the maximum current. The limit settings for different currents are shown in the
following table. The limit is a percentage of the device’s nominal current.

Frequency converter

model

Nominal current [A]

003

2.4

006

5.6

Switch S7

Current

Limit [%]

003 [A]

006

[A]

Motor Example

-1

-2

-3

003

006

0

1

0

150 % (*)

3.6

7.7

2 x MF06MA200

2 x MF06LA200,
2 x MF06LA100,
4 x MF06MA200

1

1

1

130 %

3.1

6.6

1

1

0

120 %

2.9

6.1

0

0

0

110 %

2.6

5.6

MF06LA200

1

0

1

100 %

2.4

5.1

0

0

1

90 %

2.2

4.6

MF06MA200

2 x MF06MA200,

MF06LA200, MF06LA100

1

0

0

80 %

1.9

4.1

0

1

1

70 %

1.7

3.6

MF06MK200 35Hz

MF06MA200

(*) Factory default setting.