2 checks before the first run 1 – R&M Materials Handling VARIABLE SPEED CONTROLS ControlMaster NXT Service Manual User Manual

Page 37

Advertising
background image

R&M Materials Handling, Inc.

4501 Gateway Boulevard

Springfield, Ohio 45502

P.: (937) 328-5100

FAX: (937) 325-5319

37/53

R&M Materials Handling, Inc. reserves the right to alter or amend the above information without notice.

6.2

Checks before the first run

1

Check that the main power is switched off.

2

When installing a new unit, disconnect the motor (U / T1, V /
T2, W / T3) cables to prevent damage to the frequency
converter.

Measure the insulation resistance of the motor windings
(each phase to ground). Insulation resistance requirement for
new motor:

Cold motor (10..40 °C):

5 M

Warm motor (40 °C or more):

1 M

If insulation resistance is less that requirement the motor
shall be dried.

3

Reconnect the motor cables and check the thightness of the
other cables.

4

Check that the external connections and selected control
parameters (switches) are set according to the application.