5.2.3 S2 Minimum driving frequency in traveling movement application

This switch group adjusts the minimum driving frequency of the motor. The switch settings are shown in the
following table. The selected motor nominal frequency defines which part of the table is used.

Switch S2

Minimum driving frequency

-1

-2

-3

Minimum frequency for

100/120 Hz motor

Minimum frequency for

80 Hz motor

Minimum frequency for

35 Hz motor

0

1

1

12

24

4

0

0

0

14

10

5

0

0

1

16

12

6

1

0

1

20

14

7

1

0

0

23

20

8

0

1

0

26

18

9

1

1

0

28

16

10

1

1

1

30

22

3