5.2

Switch settings in traveling movement application

Converter’s default application is traveling movement application. Application can be changed with switch group
S10-2.

Switch S10- 2

Chain hoist lifting application

0

The chain hoist lifting application is not active.

1

The chain hoist lifting application is active.

In traveling movement application ie. when chain hoist lifting application is not active the switches must be set
according to the descriptions in the following sections.

5.2.1 S9 Motor nominal frequency in traveling movement application

The motor’s nominal frequency and voltage are selected according to the values presented in the following table. If
the first alternative is selected and the mains voltage is 400 V, the maximum frequency (switch S1) must not
exceed 100 Hz.

Switch S9

Motor nominal frequency

Motor nominal voltage

- 1

- 2

0

0

100Hz / 120Hz

400 V / 460 V

0

1

80Hz

400 V

1

0

35Hz

400 V

1

1

Parameter fault

Parameter fault