5.2.2 S1 Maximum driving frequency in traveling movement application

This switch group adjusts the maximum driving frequency of the motor. The switch settings are shown in the
following table. The selected motor nominal frequency (switch group S9) defines which column of the table is used.
The maximum driving frequency shall not be set higher than the nominal frequency of the motor.

Note: The 100 Hz nominal frequency may be exceeded only if the line voltage is at least 460V.

Switch S1

Maximum driving frequency

-1

-2

-3

Maximum frequency for

100/120 Hz motor

Maximum frequency for

80 Hz motor

Maximum frequency for

35 Hz motor

1

1

1

50

55

26

1

1

0

60

60

28

1

0

1

70

65

30

1

0

0

85

70

33

0

1

0

95

75

35

0

0

0

100

80

19

0

1

1

110(*)

45

21

0

0

1

120(*)

50

24

(*) May only be used if the line voltage is at least 460V.