DEH-4567B

EntelliGuard TU Trip Units: UL/ANSI Models

Appendix E: GTU Pin Out Diagrams

©2012 General Electric All Rights Reserved

93

Table E-4: Pin Out for Legacy Breakers

Pin # RMS7

RMS9C

RMS9D

Signal Description

1

TRIPPWR +

N/C

TRIPPWR +

Main Flux Shifter +

2

N/C

PL_PWR

Remote Close

3

FANOUT

PHAHII

PBII HiBreak Air Core

4

N/C

PHBHII

PBII HiBreak Air Core

5

GFZIN+

PHCHII

PBII HiBreak Air Core

6

Keying Pin

GFZIN-

Keying Pin

Placement Aid for Connector

7

DGND

GFZOUT+

DGND

8

DGND

GFZOUT-

DGND

Contact Position Switch

9

/ST

Commnet -

/ST

Trip Signal from PBII Shunt Trip

10

DGND

Phase A High Inst. CT

DGND

Shunt Trip Reference

11

UVR_24 V

Phase B High Inst. CT

UVR_24 V

24 Volt Signal From PBII UVR

12

IPC +

Phase C High Inst. CT

IPC

Factory Test Communications

13

Commnet +

FANON

Fan Signal for 5000A AKR

14

24V EXTRN

Phase A High Inst. CT Rtn

24V EXTRN

24V Control Power +

15

DGND

Phase B High Inst. CT Rtn

DGND

24V Control Power -

16

Phase C High Inst. CT Rtn

VC

Phase C Voltage Input

17

Phase N CT White

VA

Phase A Voltage Input

18

FLUXSHT -

Phase A CT Return

FLUXSHT -

Main Flux Shifter -

19

Phase B CT Return

PL_RTN

Remote Close

20

Phase C CT Return

PHAHIR

PBII HiBreak Air Core

21

Phase N CT Return

PHBHIR

PBII HiBreak Air Core

22

Phase A CT Black

PHCHIR

PBII HiBreak Air Core

23

Phase B CT Black

24

BKRPOS

Phase C CT Black

BKRPOS

Contact position Switch

25

BA_MLR_P

Phase C Voltage Conditioner

BA_MRL_P

Bell Alarm Fire +

26

BA_MLR_P

IPC

BA_MRL_P

Lock Out Fire +

27

DGND

DGND

UVR 24V Ground

28

AGND

Flux Shifter -

AGND

Analog Ground

29

Phase B Voltage Conditioner

HMNET-C

Commnet +

30

GFZOUT+

Zone Select Out +

31

Aux Microswitch

GFZIN+

Zone Select In +

32

DGND

Flux Shifter +

DGND

Draw Out Switch Return

33

Phase A Voltage Conditioner

VB

Phase B Voltage Input

34

PHA+

Aux Microswitch

PHA

Phase A CT

35

PHA-

-24v Control

CTCOM

Phase A CT Return

36

PHB+

+24v Control

PHB

Phase B CT

37

PHB-

NA

CTCOM

Phase B CT Return

38

PHC+

NA

PHC

Phase C CT

39

PHC-

NA

CTCOM

Phase C CT Return

40

NA

N/C

41

FS2_RTN

NA

MRL_RTN

Lock Out Fire -

42

FS2_RTN

NA

BA_RTN

Bell Alarm Fire -

43

ST_24 V

NA

ST_24 V

24V from Shunt Trip

44

/UVR

NA

/UVR

Trip Signal from UVR

45

DGND

NA

DGND

Commnet -

46

NA

GFZOUT -

Zone Select Out -

47

NA

GFZIN -

Zone Select In -

48

NA

D_OUT

Draw Out Switch Input

49

PHN+

NA

CTN

Neutral CT

50

PHN-

NA

CTCOM

Neutral CT Return