Table c4: discrete inputs from gtu – GE Industrial Solutions EntelliGuard TU Trip Units User Manual

Page 99

Advertising
background image

DEH-4567B

EntelliGuard TU Trip Units: UL/ANSI Models

Appendix C: Modbus Register Map

©2012 General Electric All Rights Reserved

89

Table C-4: Discrete Inputs from GTU

Register
Address

Modicon
Address

Parameter

Value

0

10001

Long time pickup state

IN(1)/OUT(0)

1

10002

Short time pickup state

IN(1)/OUT(0)

2

10003

GF Sum Pickup state

IN(1)/OUT(0)

5

10006

Relay 1 Status

ON(1)/OFF(0)

6

10007

Relay 2 Status

ON(1)/OFF(0)

7

10008

Relay 3 Status

ON(1)/OFF(0)

8

10009

Relay 4 Status

ON(1)/OFF(0)

9

10010

Input 1 Status

ON(1)/OFF(0)

10

10011

Input 2 Status

ON(1)/OFF(0)

11

10012

Input 3 Status

ON(1)/OFF(0)

12

10013

Input 4 Status

ON(1)/OFF(0)

13

10014

Bell alarm actuation

ON(1)/OFF(0)

14

10015

Bell alarm/lockout actuation ON(1)/OFF(0)

15

10016

Shunt 1 Trip status

ON(1)/OFF(0)

16

10017

Shunt 2 Trip Status

ON(1)/OFF(0)

17

10018

UVR 1 Trip Status

ON(1)/OFF(0)

18

10019

UVR 2 Trip Status

ON(1)/OFF(0)

20

10021

Fan status

ON(1)/OFF(0)

21

10022

Voltage Unbalance Status

0 - Normal
1 - Pickup

22

10023

Under Voltage Status

0 - Normal
1 - Pickup

23

10024

Over Voltage Status

0 - Normal
1 - Pickup

24

10025

Current Unbalance Status

0 - Normal
1 - Pickup

25

10026

Power Reversal Status

0 - Normal
1 - Pickup

26

10027

V Detect

ON(1)/OFF(0)

27

10028

Breaker position

ON(1)/OFF(0)

28

10029

Breaker Ready to close

ON(1)/OFF(0)

29

10030

Spring Charge

ON(1)/OFF(0)

30

10031

Breaker closed and
connected

ON(1)/OFF(0)

31

10032

Breaker Connected

ON(1)/OFF(0)

32

10033

Test Position

ON(1)/OFF(0)

33

10034

Disconnect Indication

ON(1)/OFF(0)

34

10035

Cassette Indication

ON(1)/OFF(0)

35

10036

Draw Out

ON(1)/OFF(0)

40

10041

OffsetCalibrationStatus

1 - Complete
0 - Pending

41

10042

HGCalibrationStatus-All

1 - Complete
0 - Pending

42

10043

LGCalibrationStatus-All

1 - Complete
0 - Pending

43

10044

CTGFCalibrationStatus-All

1 - Complete
0 - Pending

44

10045

Remote Close

ON(1)/OFF(0)

49

10050

VoltCalibrationStatus-All

1 - Complete
0 - Pending

50

10051

PowerCalibrationStatus-All

1 - Complete
0 - Pending

51

10052

GTU Tripped

YES(1)/NO(0)

Register

Address

Modicon

Address

Parameter

Value

52

10053

Auxiliary Power

ON(1)/OFF(0)

53

10054

Battery Available

YES(1)/NO(0)

54

10055

WFC Data Available

YES(1)/NO(0)

55

10056

GF CT Status

0 - Normal
1 - Pickup

56

10057

Voltage Unbalance Alarm
Status

0 - Normal
1 - Alarm

57

10058

Under Voltage Alarm Status 0 - Normal

1 - Alarm

58

10059

Over Voltage Alarm Status

0 - Normal
1 - Alarm

59

10060

Current Unbalance Alarm
Status

0 - Normal
1 - Alarm

60

10061

Power Reversal Alarm Status 0 - Normal

1 - Alarm

61

10062

GF Sum Alarm Status

0 - Normal
1 - Alarm

62

10063

GF CT Alarm Status

0 - Normal
1 - Alarm

63

10064

Current Alarm 1 Status

0 - Normal
1 - Alarm

64

10065

Current Alarm 2 Status

0 - Normal
1 - Alarm

65

10066

RELT Status

0 - OFF
1 - ON