GE Industrial Solutions EntelliGuard TU Trip Units User Manual

Page 89

Advertising
background image

DEH-4567B

EntelliGuard TU Trip Units: UL/ANSI Models

Appendix C: Modbus Register Map

©2012 General Electric All Rights Reserved

79

Register

Address

Modicon

Address Variable Name

Allowable Values

Notes

268

40269

Power Reversal
Delay

0 - Off
1- 1
2- 2
3- 3
4- 4
5- 5

6- 6
7- 7
8- 8
9- 9
10- 10

11- 11
12- 12
13- 13
14-14
15-15

269

40270

Power Direction
Setting

0 - Line to Load
1 - Load to Line

270

40271

Power Demand
Interval

1 - 5
2 - 10
3 - 15

4 - 20
5 - 15

..
12 – 60

271

40272

Relay1 (Output1)
Function

1 - Group 1
2 - Group 2
3 - Group 3
4 - Group 4

5 - Group 5
6 - Group 6
7 - Group 7
8 - Group 8

9 - Group 9
10 - Group 10
11 - Group 11

If RELT is optioned, Output 1 will have
Group 7 and it cannot be changed

272

40273

Relay2 (Output2)
Function

1 - Group 1
2 - Group 2
3 - Group 3
4 - Group 4

5 - Group 5
6 - Group 6
7 - Group 7
8 - Group 8

9 - Group 9
10 - Group 10
11 - Group 11

273

40274

Relay3 (Output3)
Function

1 - Group 1
2 - Group 2
3 - Group 3
4 - Group 4

5 - Group 5
6 - Group 6
7 - Group 7
8 - Group 8

9 - Group 9
10 - Group 10
11 - Group 11

GTU 40 Only (IEC Version)

274

40275

Relay4 (Output4)
Function

1 - Group 1
2 - Group 2
3 - Group 3
4 - Group 4

5 - Group 5
6 - Group 6
7 - Group 7
8 - Group 8

9 - Group 9
10 - Group 10
11 - Group 11

GTU 40 Only (IEC Version)

275

40276

Input 1 Function 0 - None

2 - Reduce Instantaneous

3 - Reset Relays

276

40277

Input 2 Function 0 - None

1 - Trip Breaker

2 - NA
3 - Reset Relays

277

40278

Input 3 Function 0 - None

1 - Trip Breaker

2 - NA
3 - Reset Relays

GTU 40 Only (IEC Version)

278

40279

Input 4 Function 0 - None

1 - Trip Breaker

2 - NA
3 - Reset Relays

GTU 40 Only (IEC Version)

285

40286

Waveform
Capture

0 - Disable
1 - Manual
2 - Over Current

3 - Protection
Relays
4 - Current Alarm 1

5 - Current Alarm
2
6 - All

286

40287

Language

0 - English
1 - French

2 - Spanish
3 - German

4 - Chinese

287

40288

Time Sync Year

8 bit

Date and time values are pre-loaded for
some point in the future in registers 287
– 293.
At the date and time entered in those
registers, command 103 is sent to the
device, which updates the device’s
current date/time settings with the new
settings.

288

40289

Time Sync Month 8 bit

289

40290

Time Sync Date

8 bit

290

40291

Time Sync Day

8 bit

291

40292

Time Sync Hour

8 bit

292

40293

Time Sync Minute 8 bit

293

40294

Time Sync Second 8 bit

294

40295

Health status
output type

0 - NC
1 - NO

295

40296

HSI Output
Polarity

296

40297

Current Alarm 1
Pickup On

1 - 0.5
2 - 0.55
3 - 0.60
4 - 0.65

5 - 0.70
6 - 0.75
7 - 0.80
8 - 0.85

9 - 0.90
10 - 0.95
11 - 1.00