EntelliGuard TU Trip Units: UL/ANSI Models

DEH-4567B

Appendix C: Modbus Register Map

86

©2012 General Electric All Rights Reserved

Register

Address

Modicon

Address Description

Range

147

30148

Event 9

0 - No Event
1 - Long Time Trip
2 - Short Time Trip
3 - Instantaneous Trip
4 - Ground Fault Sum
Trip
5 - Ground Fault CT
Trip

6 - Power Reversal
Trip
7 - Voltage
Unbalance Trip
8 - Under Voltage
Trip
9 - Current
unbalance trip

10 - Overvoltage trip
11 - Undervoltage
Release 1 Trip
12 - Undervoltage
Release 2 Trip
13 - Shunt 1 Trip
14 - Shunt 2 Trip
15 - Watchdog

148

30149

Year

8 bit

149

30150

Month

8 bit

150

30151

Date

8 bit

151

30152

Hour

8 bit

152

30153

Minute

8 bit

153

30154

Second

8 bit

154

30155

Phase

8 bit

155

30156

Event Specific - Low 16 bits

16 bit

156

30157

Event Specific - Hi 16 bits

16 bit

157

30158

Event 10

0 - No Event
1 - Long Time Trip
2 - Short Time Trip
3 - Instantaneous Trip
4 - Ground Fault Sum
Trip
5 - Ground Fault CT
Trip

6 - Power Reversal
Trip
7 - Voltage
Unbalance Trip
8 - Under Voltage
Trip
9 - Current
unbalance trip

10 - Overvoltage trip
11 - Undervoltage
Release 1 Trip
12 - Undervoltage
Release 2 Trip
13 - Shunt 1 Trip
14 - Shunt 2 Trip
15 - Watchdog

158

30159

Year

8 bit

159

30160

Month

8 bit

160

30161

Date

8 bit

161

30162

Hour

8 bit

162

30163

Minute

8 bit

163

30164

Second

8 bit

164

30165

Phase

8 bit

165

30166

Event Specific - Low 16 bits

16 bit

166

30167

Event Specific - Hi 16 bits

16 bit

167

30168

Long Time Trip Count

16 bit

168

30169

Short Time Trip Count

16 bit

169

30170

Instantaneous Trip Count

16 bit

170

30171

Ground Fault Sum Trip Count

16 bit

172

30173

Power Reversal Trip Count

16 bit

173

30174

Voltage Unbalance Trip Count

16 bit

174

30175

Under Voltage Trip Count

16 bit

175

30176

Current unbalance Trip Count

16 bit

176

30177

Overvoltage trip Count

16 bit

177

30178

Undervoltage Release 1 Trip Count

16 bit

178

30179

Undervoltage Release 2 Trip Count

16 bit

179

30180

Shunt 1 Trip Count

16 bit

180

30181

Shunt 2 Trip Count

16 bit

181

30182

Total Trip Count

16 bit

195

30196

GF CT Trip Count

8 bit

196

30197

Software Rev Primary

8 bit

198

30199

GTU in Diagnostic Mode

0 - No

1 - Yes

227

30228

Breaker Postion

1 - CLOSE

0 - OPEN

228

30229

Error Code log

00 - No Error
02 - BIM Error
03 - Data Flash R/W

05 - EEPROM

Malfunction

08 - Incorrect Rating

Plug