EntelliGuard TU Trip Units: UL/ANSI Models

DEH-4567B

Appendix C: Modbus Register Map

80

©2012 General Electric All Rights Reserved

Register

Address

Modicon

Address Variable Name

Allowable Values

Notes

297

40298

Current Alarm 1
Pickup Off

1 - 0.5
2 - 0.55
3 - 0.60
4 - 0.65

5 - 0.70
6 - 0.75
7 - 0.80
8 - 0.85

9 - 0.90
10 - 0.95
11 - 1.00

298

40299

Current Alarm 2
Pickup On

1 - 0.5
2 - 0.55
3 - 0.60
4 - 0.65

5 - 0.70
6 - 0.75
7 - 0.80
8 - 0.85

9 - 0.90
10 - 0.95
11 - 1.00

299

40300

Current Alarm 2
Pickup Off

1 - 0.5
2 - 0.55
3 - 0.60
4 - 0.65

5 - 0.70
6 - 0.75
7 - 0.80
8 - 0.85

9 - 0.90
10 - 0.95
11 - 1.00

300

40301

Bell Alarm (Bell
Alarm 1)

0 - Disabled
1 - Shunt Trip
2 - UVR Trip
3 - Over Current
Trip
4 - Protective
Relay Trip
5 - Shunt, UVR
6 - Shunt, Over
Current

7 - Shunt,
Protective Relay
8 - UVR, Over
Current
9 - UVR, Protective
Relay
10 - Over Current,
Protective Relay
11 - Shunt Trip,
UVR, Over Current

12 - Shunt, UVR,
Protective Relay
13 - Shunt, Over
Current,
Protective Relay
14 - UVR, Over
Current,
Protective Relay
15 - Shunt, UVR,
Over Current,
Protective Relay

301

40302

Bell Alarm with
lockout (Bell
Alarm 2)

0 - Disabled
1 - Shunt Trip
2 - UVR Trip
3 - Over Current
Trip
4 - Protective
Relay Trip
5 - Shunt, UVR
6 - Shunt, Over
Current

7 - Shunt,
Protective Relay
8 - UVR, Over
Current
9 - UVR, Protective
Relay
10 - Over Current,
Protective Relay
11 - Shunt Trip,
UVR, Over Current

12 - Shunt, UVR,
Protective Relay
13 - Shunt, Over
Current,
Protective Relay
14 - UVR, Over
Current,
Protective Relay
15 - Shunt, UVR,
Over Current,
Protective Relay

302

40303

ZSI Short Time
Delay Band

0 - OFF
1- Band1
2- Band2
3- Band3
4- Band4
5- Band5

6- Band6
7- Band7
8- Band8
9- Band9
10- Band10
11- Band11

12- Band12
13- Band13
14- Band14
15 - Band 15
16 - Band 16
17 - Band 17

303

40304

ZSI Short Time Kst 0 - 0

1 - 2

2 - 8
3 - 18

304

40305

ZSI GF Trip Delay 0 - OFF

1 - Band1
2- Band2
3- Band3
4- Band4

5- Band5
6- Band6
7- Band7
8- Band8
9- Band9

10- Band10
11 - Band 11
12-Band 12
13-Band13
14-Band14

305

40306

ZSI GF Trip K
Value

0 - 0
1 - I

2

T 2

2 - I

2

T 3

3 - I

4

T 18

306

40307

Breaker Position 1 - CLOSE

0 - OPEN

307

40308

Waveform Trigger
Source - Manual

0 - OFF
1 - ON

308

40309

Waveform Trigger
Source - Over
Current

0 - OFF
1 - ON