Table a20: powerbreak i & ii digits 6 & 7, Table a23: zone selective interlocking digit 8 – GE Industrial Solutions EntelliGuard TU Trip Units User Manual

Page 80

Advertising
background image

EntelliGuard TU Trip Units: UL/ANSI Models

DEH-4567B

Appendix A: GTU Nomenclature

70

©2012 General Electric All Rights Reserved

Table A-18: OC and GF Protection Packages Digits 6 & 7,
WavePro when Used in UL891 Switchboards with 5 Cycle
Withstand Busing

Code Explanation
LP

LSI (S, switchable) (I, Non-switchable, used for
WavePro in Switchboards)

LQ

LSIG (S, switchable) (I, Non-switchable, used for
WavePro in Switchboards)

LR

LSIGA (S, switchable) (I, Non-switchable, used
for WavePro in Switchboards)

LS

LSIGDA* (S, G, A all switchable) (I, Non-
switchable, used for WavePro in Switchboards)

JP

Replaced by LP

JQ

Replaced by LQ

JR

Replaced by LR

JS

Replaced by LS

Table A-19: AKR, Conv. Kits with OC Protection Digits
6 & 7

Code Explanation
L3

LSI (S, switchable) (I, switchable)

L4

LSIG (S, switchable) (I, switchable)

L5

LSIGA (S, switchable) (I, switchable)

L8

LSIGDA* (S, G, A all switchable) (I, switchable)

J3

Replaced by L3

J4

Replaced by L4

J5

Replaced by L5

J8

Replaced by L8

Table A-20: PowerBreak I & II Digits 6 & 7

Code Explanation
L3

LSI (S, switchable) (I, Non-switchable)

L4

LSIG (S, switchable) (I, Non-switchable)

L5

LSIGA (S, switchable) (I, Non-switchable)

L8

LSIGDA* (S, G, A all switchable) (I, Non-
switchable)

J3

Replaced by L3

J4

Replaced by L4

J5

Replaced by L5

J8

Replaced by L8

Table A-21: EntelliGuard G ANSI and UL Low-cost ACB
Digits 6 & 7

Code Explanation
L3

LSI (S, switchable) (I, switchable ANSI only) (I is
non-switchable for AKR30S conversion kits)

L4

LSIG (S, switchable) (I, switchable ANSI only) (I is
non-switchable for AKR30S conversion kits)

L5

LSIGA (S, switchable) (I, switchable ANSI only)

L6

LSIC (S, switchable) (I, switchable ANSI only)

L7

LSICA (S, switchable) (I, switchable ANSI only)

J3

Replaced by L3

J4

Replaced by L4

J5

Replaced by L5

J6

Replaced by L6

J7

Replaced by L7

Table A-22: CVCB MTU IEC Medium Voltage OC Protection
Digits 6 & 7

Code Explanation
C1

KS (both non-switchable)

C2

KSG (all non-switchable)

C3

KSHG (K, S, G (all not switchable), H (switchable)

C4

KSHGCD (K, S, H, G and C (all switchable)

C5

KSHGCDA (K, S, H, G, C and A (all switchable)

Table A-23: Zone Selective Interlocking Digit 8

EntelliGuard G

ANSI/UL

EntelliGuard G

IEC

Power Break

I & II

WavePro, AKR,

Conv Kits

EntelliGuard

MTU

Z = ZSI, Short time and GF; user
selectable

Z

Z

Z

Z

X

T = Z + IOC ZSI; user selectable

T

T

X

T

V = RESERVED

X

X

X

W = RESERVED

X =NONE SELECTED

Advertising