EntelliGuard TU Trip Units: UL/ANSI Models

DEH-4567B

Appendix C: Modbus Register Map

76

©2012 General Electric All Rights Reserved

Register

Address

Modicon

Address Variable Name

Allowable Values

Notes

236

40237

GF Sum Alarm
Pickup

1- 0.10
2- 0.11
3- 0.12
4- 0.13
5- 0.14
6- 0.15
7- 0.16
8- 0.17
9- 0.18
10- 0.19
11 - 0.20

12- 0.21
13- 0.22
14- 0.23
15- 0.24
16- 0.25
17- 0.26
...
78- 0.87
79- 0.88
80- 0.89
81 - 0.90

82- 0.91
83- 0.92
84- 0.93
85- 0.94
86- 0.95
87- 0.96
88- 0.97
89- 0.98
90- 0.99
91- 1.00

LCD / MODBUS

ANY IEC
GTU 17 / 40 - 0.1 - 1.0 (IEC)
NON IEC
GTU D/C - 0.2 to 0.6 (sensor <=2000A)
GTU D/C - 0.2 – 0.37 (sensor 2500 &
3200A)
GTU D/C - 0.2 – 0.3 (sensor 4000A)
GTU D/C - 0.2 – 0.24 (sensor 5000A)
GTU D/C - 0.2 (6000 – 6400)

237

40238

GF Sum Alarm
Delay

0 - Off
1 - Band1
2- Band2
3- Band3
4- Band4

5- Band5
6- Band6
7- Band7
8- Band8
9- Band9

10- Band10
11- Band11
12- Band12
13- Band13
14- Band14

Band 1 for GACB only

238

40239

GF Sum Alarm K
Value

0 - 0
1 - I

2

T 2

2 - I

2

T 4.4

3 - I

4

T 19.8

239

40240

UEF Pickup

1- 0.10
2- 0.11
3- 0.12

....
89- 0.98

90- 0.99
91- 1.00

1 (0.1) only available with Aux Power

240

40241

UEF Delay

0 - Off
1- Band1
2- Band2
3- Band3
4- Band4

5- Band5
6- Band6
7- Band7
8- Band8
9- Band9

10- Band10
11- Band11
12- Band12
13- Band13
14- Band14

When UEF is used in combination with
REF, SEF, or SEF and REF, it cannot be
switched OFF

241

40242

UEF K

0 - 0
1 - I

2

T 2

2 - I

2

T 4.4

3 - I

4

T 19.8

242

40243

SEF Pickup

1- 0.10
2- 0.11
3- 0.12

....
89- 0.98

90- 0.99
91- 1.00

1 (0.1) only available with Aux Power.
The SEF Pickup must be greater than
UEF Pickup Setting.

243

40244

SEF Delay

0 - Off
1- Band1
2- Band2
3- Band3
4- Band4

5- Band5
6- Band6
7- Band7
8- Band8
9- Band9

10- Band10
11- Band11
12- Band12
13- Band13
14- Band14

The SEF Delay must be at least 0.1
second greater than UEF delay setting

244

40245

SEF K

0 - 0
1 - I

2

T 2

2 - I

2

T 4.4

3 - I

4

T 19.8

245

40246

REF Pickup

1- 0.10
2- 0.11
3- 0.12

....
89- 0.98

90- 0.99
91- 1.00

1 (0.1) only available with Aux Power

246

40247

REF Delay

0 - OFF

1 - Fixed 130ms delay

247

40248

Timeout Metering 0 - No

1 – Yes

If lcd screen is left at Metering, will go to
Home Menu after 5 minutes

258

40259

Over Voltage
Pickup

1- 110
2- 111
3-112
4- 113
5-114
6- 115
7-116
8- 117
9- 118
10- 119
11 - 120
12- 121
13- 122
14- 123

15- 124
16- 125
17- 126
18- 127
19- 128
20-129
21- 130
22- 131
23-132
24- 133
25-134
26- 135
27-136
28- 137

29- 138
30- 139
31 - 140
32- 141
33- 142
34- 143
35- 144
36- 145
37- 146
38- 147
39- 148
40-149
41- 150