Table 2-13: Over Voltage Settings

Item

Option

Over voltage
pickup

Adjustable from 110% to 150% in
increments of 1%.

Over voltage
delay

Adjustable from 1 sec to 15 sec in
increments of 1 sec. Setting this value
to OFF disables this function.

Power Reversal Relay

This function measures the direction of power flow through
the breaker and initiates a trip if a sufficient magnitude of
reverse power is detected.

Table 2-14: Power Reversal Settings

Item

Option

Power reversal
pickup

Adjustable from 10 kW to 990 kW in
increments of 10 kW.

Power reversal
delay

Adjustable from 1 sec to 15 sec in
increments of 1 sec. Setting this value
to zero (0) will disable this function.

Power Direction Setup

This function selects the normal power flow direction for
the breaker. Set this parameter to match the direction of
current flow through the breaker during normal operating
conditions. This direction setup also affects the sign of the
normal power metering displays.

Potential Transformer Voltage

Enter the primary voltage rating of the potential
transformer. The range of values is 120 V to 600 V, with an
increment of 1V. The voltage input coming into the trip unit
must be wired into using voltage conditioners which steps
the voltage down to an acceptable voltage level. See below
for voltage conditioner plate wiring diagrams.

Figure 2-6: Voltage Conditioner Plate Wiring — Wye