EntelliGuard TU Trip Units: UL/ANSI Models

DEH-4567B

General Information

6

©2012 General Electric All Rights Reserved

command to clear the waveform data in trip unit
memory.

Table 1-2: Trigger WaveForm Capture Events

Event

Waveform Capture Setpoint

Manual trigger over
communications

ON, OFF

Over current (GF, ST, LT,
Inst)

ON, OFF

Protective relays

ON, OFF

Current alarm 1

ON, OFF

Current alarm 2

ON, OFF

Event Logging

The trip unit keeps a log of the last 10 events:

• Over current trips
• Protective relay trips
• Shunt trip (PBII and Global EntelliGuard G Trip Units Only)
• Under voltage Release trip (PBII and Global EntelliGuard

G Trip Units Only)

• BIM Trip Unit Mismatch - Breaker Interface Module

(EntelliGuard G only)

NOTICE

SOFTWARE REVISION 08.00.23 AND GREATER:
If a BIM read fails the trip unit will not open the breaker,
instead it will modify its internal configuration to match the
AIC rating of the least capable breaker in the family. The
trip unit will periodically read the BIM after that, and on a
successful match the original settings will be restored.
While the BIM error persists a BIM Err message will be
displayed on the LCD.

The following information is stored with each event:

• RMS currents
• Phase
• Type of trip
• Trip counter
• Time and date stamps (Trips are logged under self

power without time stamp. Events with time stamps are
only logged when +24 VDC control power is available.)