Actual long time pickup is 112% of nominal pickup, Short time protection, Short time pickup – GE Industrial Solutions EntelliGuard TU Trip Units User Manual

Page 19: Figure 23: short time pickup time current curve

Advertising
background image

DEH-4567B

EntelliGuard TU Trip Units: UL/ANSI Models

Protection

©2012 General Electric All Rights Reserved

9

Table 2-2: Nominal Clearing Times for Fuse Shaped Long Time Bands

X =

1.5

1.5

6

6

7.2

7.2

10

10

Commit

Clear

Commit

Clear

Commit

Clear

Commit

Clear

Min F

0.67

1.54

0.025

0.085

0.025

0.085

0.025

0.085

F-2

2.0

4.40

0.025

0.085

0.025

0.085

0.025

0.085

F-3

3.6

7.98

0.025

0.085

0.025

0.085

0.025

0.085

F-4

5.6

12.5

0.025

0.085

0.025

0.085

0.025

0.085

F-5

8.1

18.0

0.032

0.100

0.025

0.085

0.025

0.085

F-6

11.2

25.0

0.044

0.13

0.025

0.085

0.025

0.085

F-7

15.1

33.8

0.059

0.16

0.028

0.094

0.025

0.085

F-8

20.0

44.7

0.078

0.20

0.038

0.114

0.025

0.085

F-9

26.1

58.4

0.102

0.26

0.049

0.14

0.025

0.085

F-10

33.8

75.4

0.13

0.32

0.064

0.17

0.025

0.085

F-11

43.3

96.8

0.17

0.41

0.082

0.21

0.025

0.085

F-12

55.3

123

0.22

0.51

0.104

0.26

0.028

0.092

F-13

70.2

157

0.27

0.64

0.13

0.33

0.036

0.109

F-14

88.9

198

0.35

0.81

0.17

0.40

0.045

0.13

F-15

112

251

0.44

1.01

0.21

0.50

0.057

0.16

F-16

141

316

0.55

1.26

0.27

0.62

0.072

0.19

F-17

178

397

0.69

1.58

0.34

0.78

0.090

0.23

F-18

224

499

0.87

1.98

0.42

0.97

0.113

0.28

Max-F

280

626

1.10

2.48

0.53

1.21

0.142

0.35

• Algorithm will not commit below 1.5 cycles, clearing time will not be less than 0.088 seconds.
• Actual Long Time pickup is 112% of nominal pickup.

SHORT TIME PROTECTION
Short Time Pickup

The Short Time Pickup function establishes the current at
which short time trip is activated. Short Time Pickup is with
a multiple of the Long Time Pickup and the choices of
pickup settings are from 1.5 to 12.0 times the Long Time
setting, xLT, in steps of 0.5 xLT.

The maximum pickup depends on breaker type and frame
as shown in Table 2-3, below:

The Short Time Pickup value tolerance band is
approximately -9% to +11% of the set point based on a
10% current sensing accuracy with the pickup calculated
with 1/ (1+Tolerance). The time current curve of short time
pickup is shown in Figure 2-3.

Figure 2-3: Short Time Pickup Time Current Curve