Table c2: inputs from gtu – GE Industrial Solutions EntelliGuard TU Trip Units User Manual

Page 92

Advertising
background image

EntelliGuard TU Trip Units: UL/ANSI Models

DEH-4567B

Appendix C: Modbus Register Map

82

©2012 General Electric All Rights Reserved

Register

Address

Modicon

Address Variable Name

Allowable Values

Notes

637

40638

638

40639

639

40640

Table C-2: Inputs from GTU

Register

Address

Modicon

Address Description

Range

14

30015

Power Peak Demand Total - Lo 32 bits

32 bit, Scaled value: 32 bit value/10

15

30016

Power Peak Demand Total - Hi 32 bits

32 bit, Scaled value: 32 bit value/10

16

30017

GTU Rev

8 bit

17

30018

Software Rev

8 bit

18

30019

Voltage Phase A

16 bit, Scaling 1:1

19

30020

Voltage Phase B

16 bit, Scaling 1:1

20

30021

Voltage Phase C

16 bit, Scaling 1:1

21

30022

Current Phase A(LO 32 bits )

32 bit, Scaling 1:1

22

30023

Current Phase A(HI 32 bits )

32 bit, Scaling 1:1

23

30024

Current Phase B(LO 32 bits )

32 bit, Scaling 1:1

24

30025

Current Phase B(HI 32 bits )

32 bit, Scaling 1:1

25

30026

Current Phase C(LO 32 bits )

32 bit, Scaling 1:1

26

30027

Current Phase C(HI 32 bits )

32 bit, Scaling 1:1

27

30028

Current Phase N(LO 32 bits )

32 bit, Scaling 1:1

28

30029

Current Phase N(HI 32 bits )

32 bit, Scaling 1:1

29

30030

Rating Plug Value

0 - 0
1 - 150
2 - 200,
3 - 225,
4 - 250,
300,
350,
400,
450,
500,
600,
630,
700,

800,
900,
1000,
1100,
1200,
1250,
1500,
1600,
1900,
2000,
2200,
2400,
2500,

3000,
3200,
3600,
4000,
5000,
6000,
100,
750,
3500,
4500,
6400,
60,
80

31

30032

Energy Total ( 0-15 bits ) Divide value by 10 to
get kWH

64 bit, Scaled value = [(Register 35 * 2^32) + (32 bit value in
registers 31 + 32)]/10

32

30033

Energy Total (16-31 bits) Divide value by 10 to
get kWH

64 bit, Scaled value = [(Register 35 * 2^32) + (32 bit value in
registers 31 + 32)]/10

33

30034

Reserved

34

30035

Reserved

35

30036

Energy Rollover Count

16 bit, Scaled value = [(Register 35 * 2^32) + (32 bit value in
registers 31 + 32)]/10

36

30037

Power Factor Phase A

16 bit

37

30038

Power Factor Phase B

16 bit

38

30039

Power Factor Phase C

16 bit

39

30040

Power Factor Total

16 bit

40

30041

Power Real Phase A - Lo 16 bits

32 bit (Divide value by 10 to get KW) Scaled value: 32 bit value/10

41

30042

Power Real Phase A - Hi 16 bits

32 bit (Divide value by 10 to get KW) Scaled value: 32 bit value/10

42

30043

Power Real Phase B - Lo 16 bits

32 bit (Divide value by 10 to get KW) Scaled value: 32 bit value/10

43

30044

Power Real Phase B - Hi 16 bits

32 bit (Divide value by 10 to get KW) Scaled value: 32 bit value/10

44

30045

Power Real Phase C - Lo 16 bits

32 bit (Divide value by 10 to get KW) Scaled value: 32 bit value/10

45

30046

Power Real Phase C - Hi 16 bits

32 bit (Divide value by 10 to get KW) Scaled value: 32 bit value/10

46

30047

Power Real Phase Total - Lo 16 bits

32 bit (Divide value by 10 to get KW) Scaled value: 32 bit value/10

47

30048

Power Real Phase Total - Hi 16 bits

32 bit (Divide value by 10 to get KW) Scaled value: 32 bit value/10

48

30049

Power Reactive Phase A - Lo 16 bits

32 bit (Divide value by 10 to get KW) Scaled value: 32 bit value/10