In the “Test” position AC input power to the drive will be applied and the inverter

will run at the speed set in using the Hand/Off/Auto functionality. However, the

“Test” position disables drive output contactor’s operation and power will not be

applied from the inverter to the motor even if the Drive/Off/Bypass selector is in

the “Drive” position. The “Test” setting will also be operational when the

Drive/Off/Bypass switch is in the “Bypass” position allowing the inverter to be

operated without interrupting power to the motor.

In the “Normal” position AC input power to the drive will be applied and the

inverter will operate according to the setting of the H-O-A and Drive/Off/Bypass

switches. Power can be applied from the inverter to the motor only if the

Drive/Off/Bypass selector is in the “Drive” position.


Drive/Off/Bypass Selector

The setting of this selector switch determines whether power to the motor will
be from the adjustable frequency drive (“Drive” position) or directly from the AC

line (“Bypass” position). This selector can be changed “on-the-fly” without first

completely stopping the motor. However, when changing from “Drive” to

“Bypass” mode a short delay is required to be inserted by the operator

(approximately 10 seconds) to allow time for the motor’s rotor flux to decay

prior to applying AC line power. If your panel includes the optional “automatic

bypass” functionality the operator can switch directly from “Drive” to “Bypass”

with pausing in the “Off” position. The required time delay is automatically

inserted to allow time for the motor’s flux to decay.


When changing from “Bypass” to “Drive” mode the drive will utilize the inherent

catch-a-spinning motor feature for a smooth transfer.

If your bypass panel is configured for automatic transfer to bypass, then in the

event of a drive fault during “Drive” operation the panel’s control logic will

automatically transfer the motor from drive to bypass (i.e., across-the-line)

operation.







DEH40652

– Page 4

AN 11-2021 Rev 06, 12/16/2011

CAUTION: Please see the instructio

ns in the “Adjustments” section of

this manual regarding the setting of this time delay. An improper setting could
result in damage to your motor and/or driven equipment.

WARNING: Although input power is removed from the drive in the

“Isolate” position this does not guarantee that dangerous voltage levels
are absent. The AF 650 GP drives contain capacitors, which can
maintain dangerous voltage levels for an extended period following
removal of AC input power. Details of waiting time are given above